Specifications

31
Combination Full Voltage Reversing Starter Units (FVR) - Bulletin 2106 and 2107
These combination full voltage reversing starter units are supplied with an
Allen-Bradley Bulletin 505 reversing starter and either a fusible disconnect or a circuit
breaker. The Bulletin 2106 and 2107 starters are rated for NEMA sizes 1 through 5 and
are mechanically and electrically interlocked to avoid both contactors being closed
simultaneously. Each unit is provided as a NEMA Class I, Type B-T unit with terminals
mounted in the unit for connection to remote devices. Full voltage reversing starter
units are available with a eutectic alloy, E1 Plus or E3 Plus electronic overload relay.
Bulletin 2106 and 2107 - Full Voltage Reversing Starter Unit with Fusible Disconnect Switch or Circuit Breaker (FVR)
NEMA
Size
Horsepower Bulletin 2106 Bulletin 2107
208V 240V 380…415V 480/600V
Fuse Clip Space
Factor
(1)
(1) Adding options may increase the space factor of the unit.
Circuit
Breaker
Frame
Space
Factor
(1)
Rating
(Amperes)
Class
1 0.125…7.5 0.125…7.5 0.125…10 0.125…10
30 CC, J, R, H, HRCII-C 1.5 MCP,
MCP-ELC,
I3C, I3C-CL,
I6C
1.5
60 J, R, H, HRCII-C
2 10 10…15 15…25 15…25
30, 60, 100 J, R, H, HRCII-C
J, R, H, HRCII-C J
1.5 1.5
100 R, H, HRCII-C 2.0
3 15…25 20…30 30…50 30…50
60, 100, 200 J, R, H, HRCII-C
J, R, H, HRCII-C
J, R, H, HRCII-C
3.0 2.5
4 30…40 40…50 60…75 60…100
100, 200, 400 J, R, H, HRCII-C
J, R, H, HRCII-C J
4.0 MCP,
MCP-ELC,
JD3D, JD6D
4.0
5 50…75 60…100 100…150 125…200
200, 400, 600 J, R, H, HRCII-C
J, R, H, HRCII-C J
6.0, 20”W MCP, JC3D,
K3D, JD6D,
K6D
6.0, 20”W