Specifications
30
Unit Types
You can choose from a variety of units including contactor and starter units, metering units, main and feeder units, lighting
and power panel units, transformer units, combination soft starter units, variable frequency AC motor drive units and
programmable controller units. Catalog numbers and complete selection rules can be found in the CenterONE®
configuration software or the CENTERLINE 2100 Motor Control Centers Catalog, publication 2100-CA001
.
Contactor and Starter Units
Combination Full-voltage Lighting Contactor Units (FVLC) -
Bulletin 2102L and 2103L
These combination lighting contactor units are supplied with an Allen-Bradley
Bulletin 500L AC contactor and either a fusible disconnect or circuit breaker. They are
rated 30…300 A. Each unit is provided as a NEMA Class I, Type B-T unit with terminals
mounted in the unit for connection to remote devices. These full voltage reversing units
are available with E1 Plus and E3 Plus electronic overload relays.
Bulletin 2102L and 2103L - Full Voltage Lighting Contactor Unit with Fusible Disconnect Switch or
Circuit Breaker (FVLC)
Rating (A) Transformer Primary Switching kVA Bulletin 2102L Bulletin 2103L
208V 240V 380V…
415V
480V 600V
Fuse Clip Space
Factor
(1)
(1) Adding options may increase the space factor of the unit.
Circuit
Breaker
Frame
Space
Factor
(1)
1∅ 3∅ 1∅ 3∅ 1∅ 3∅ 1∅ 3∅ 1∅ 3∅
Rating
(Amperes)
Class
30 1.2 3.6 2.4 4.3 2.8 7.1 4.9 8.5 6.2 11
30 CC, J 0.5 I3C, I6C 0.5
30 1.2 3.6 2.4 4.3 2.8 7.1 4.9 8.5 6.2 11
30 CC, J, R,
H
1.0 I3C-CL ,
I3C, I6C
1.0
DUAL 30 1.23.62.44.32.8 7.1 4.98.56.211
— — — I3C, I6C 1.5
60 2.1 6.3 4.1 7.2 6.8 11.8 8.3 14 10 18
30, 60 J, R, H 1.0 I3C-CL ,
I3C, I6C
1.0
DUAL 60 2.1 6.3 4.1 7.2 6.8 11.8 8.3 14 10 18
— — — I3C, I6C 1.5
100 4.1 12 8.1 14 13.3 23.3 16 28 20 35
60, 100 J, R, H 2.5 I3C-CL,
I3C, I6C
1.5
200 6.8 20 14 23 22.5 39 27 47 34 59
100, 200 3.0 JD3D,
JD6D
2.5
300 1441274745 78.3549468117
200, 400 4.0 K3D, K6D 3.5