Specifications
21
Section Dimensions
The standard dimensions of a vertical section are
90 in. high x 20 in. wide x 15 in. deep
(2286 mm x 508 mm x 381 mm).
Vertical sections are also available as 20 in. deep (508 mm).
Some vertical sections may be wider than 20 in. (508 mm)
due to larger equipment or optional vertical wireway.
Optional 71 in. (1791 mm) reduced height vertical sections
are available. These sections can be either 15 in. (381 mm)
or 20 in. (508 mm) deep and each 71 in. high vertical
section accommodates standard plug-in units up to and
including 4.5 space factors.
Dimensions are shown as in. (mm).
Approximate Weight
This table lists approximate weights for MCC sections.
Many factors (number of units, horizontal power bus,
wireway width, section depth and width) affect the weight
of the sections. Weight is also added when the product is
packaged for shipping.
20…35
(508…889)
15 or 20
(381 or 508)
71 or 90
(1791 or 2286)
6 (152.4)
6 (152.4)
78 (1981)
4.37 or 9.37
(111 or 238)
Section Dimensions
Height 90 in. (2286 mm) standard;
71 in. (1790 mm) available
Width 20 in. (508 mm) standard; wider sections available for
larger equipment in 5 in. (127 mm) increments
Depth Front mounted 15 in. (381 mm) or 20 in. (508 mm)
Back-to-back 30 in. (762 mm) or 40 in. (1016 mm)
Vertical
Wireway
4.37 in. (111 mm) wide standard;
9.37 in. (238 mm) wide available
Approximate Weight
MCC Section Dimensions NEMA Type 1 , 1G or 12
lb (kg) per section
(1)
(1) Weights are for a typical motor control center with four units per
section. Weights do not include packaging. Refer to packing slip
shipped with you MCC for exact shipping weights.
15”/20” D, 20” W, 90” H 500 (227)
15”/20” D, 25” W, 90” H 575 (261)
15”/20” D, 30” W, 90” H 600 (272)
15”/20” D, 35” W, 90” H 650 (295)