Technical data
19
8. Faults caused by boiler’s wrong exploitation
Problem Cause Remedy suggested
boiler doesn’t reach the
temperature needed
faulty burning up check „Burning up”
to moist wood humidity control - use wood at right parameters
primary air conduit choked call service - facility out of the warranty
secondary air conduit choked call service - facility out of the warranty
smoke tube of heat exchanger
choked
clean with a cleaning shield or call service-
facility out of the warranty
wrong regulation of the air and
wood gas
call service - facility out of the warranty
nozzle damaged replacement - out of the warranty
fan’s gasket damaged replacement - out of the warranty
fan damaged replacement - out of the warranty
smoke out of the cleaning
cover
leak on a seal rope
door regulation or call service – out of the
warranty
seal rope worn rope’s replacement - out of the warranty
cover warped - overheating
cover’s replacing or call service- out f the
warranty
smoke coming out while
loading (little smoke is
acceptable)
intensive - Heavy wind blows the
fumes into the chimney
consider the montage of chimney ue
succouring elements, for instant the „Rotowent”
ones
wrong chimney parameters
consult a chimney sweep, the need of new
chimney ue building
smoke out of the boiler’s
door
leak on a seal rope
door regulation
(according to the 7.4. description)
seal rope worn
rope’s replacement or call service
- out of the warranty
door damaged door’s replacement
regulator doesn’t work
power shortage check the installation’s protection
fuse damaged fuse’s replacement
live wire conduit damaged connection and wire’s inspection
temperature sensor damaged call service
regulator damaged call service
fan out of order
thermal protection worked check „boiler’s overheating” description
no power in regulator check „power shortage in regulator”
fan damaged call service - fan’s replacement
regulator damaged call service
fan blocked inspect and clean the fan