Instruction manual
8.0 DETAILED DATA SETTING SM425 INSTRUCTION MANUAL
Figure 8-12 Input Contacts Display
8.5.3 Default Input Contact Setting
The default contact input setting is “No function” for both contacts.
8.6 Other Settings
8.6.1 Setting the Date and Time
Use the following procedure to set the current date and time. Time and date must be set for automatic
calibrations and blowbacks to work:
1. Press the Setup key in the Basic Panel display screen.
2. Select “Setup” in the Execution/Setup display screen.
3. Select “Others” in the “Commissioning” (Setup) display screen. The “Others” display screen then
appears, as shown in Figure 8-13.
4. Select Clock. The Clock display screen then appears, as shown in Figure 8-14.
5. Select Set date to display the numeric-data entry display screen. To set the date to June 21,
2000, enter 2106000 and press the [Enter] key. The display then returns to the Clock screen.
6. Select Set time. Enter the time in a 24-hour format. Type 1430 in the numeric-data entry display
screen to set time to 2:30 pm. Press the [Enter] key. The seconds are reset to 00.
Figure 8-13 Other Settings
42500001 REV A 133