4114 Universal transmitter No. 4114V104-UK F r o m s e r. n o .
DK PR electronics A/S tilbyder et bredt program af analoge og digitale signalbehandlingsmoduler til industriel automation. Programmet består af Isolatorer, Displays, Ex-barrierer, Temperaturtransmittere, Universaltransmittere mfl. Vi har modulerne, du kan stole på i selv barske miljøer med elektrisk støj, vibrationer og temperaturudsving, og alle produkter opfylder de strengeste internationale standarder. Vores motto »Signals the Best« er indbegrebet af denne filosofi – og din garanti for kvalitet.
UNIVERSAL TRANSMITTER 4114 CONTENTS Warning............................................................................... Symbol identification........................................................... Safety instructions............................................................... Declaration of conformity.................................................... How to demount system 4000............................................ When front LED lights red / display shows AO.ER.............
WARNING GENERAL This device is designed for connection to hazardous electric voltages. Ignoring this warning can result in severe personal injury or mechanical damage. To avoid the risk of electric shock and fire, the safety instructions of this manual must be observed and the guidelines followed. The specifications must not be exceeded, and the device must only be applied as described in the following. Prior to the commissioning of the device, this manual must be examined carefully.
SYMBOL IDENTIFICATION Triangle with an exclamation mark: Warning / demand. Potentially lethal situations. The CE mark proves the compliance of the device with the essential requirements of the directives. The double insulation symbol shows that the device is protected by double or reinforced insulation. SAFETY INSTRUCTIONS DEFINITIONS Hazardous voltages have been defined as the ranges: 75 to 1500 Volt DC, and 50 to 1000 Volt AC.
Mounting and connection of the device should comply with national legislation for mounting of electric materials, i.e. wire cross section, protective fuse, and location. Descriptions of input / output and supply connections are shown in the block diagram and side label. The following apply to fixed hazardous voltages-connected devices: The max. size of the protective fuse is 10 A and, together with a power switch, it should be easily accessible and close to the device.
DECLARATION OF CONFORMITY As manufacturer PR electronics A/S Lerbakken 10 DK-8410 Rønde hereby declares that the following product: Type: 4114 Name: Universal transmitter is in conformity with the following directives and standards: The EMC Directive 2004/108/EC and later amendments EN 61326-1 For specification of the acceptable EMC performance level, refer to the electrical specifications for the device.
HOW TO DEMOUNT SYSTEM 4000 First, remember to demount the connectors with hazardous voltages. Picture 1: Detach the device from the DIN rail by lifting the bottom lock. When front LED lights red / display shows AO.ER PR 4114 is designed as a SIL 2 device with a high safety level. Therefore, a continuous measurement of the outgoing current is carried out on a 4...20 mA and 20...4 mA output signal.
UNIVERSAL TRANSMITTER PReasy 4114 • Input for RTD, TC, Ohm, potentiometer, mA and V • 2-wire supply > 16 V • FM-approved for installation in Div. 2 • Output for current and voltage • Universal AC or DC supply Advanced features • Programmable by way of detachable display front (4501), process calibration, signal simulation, password protection, error diagnostics and help text available in several languages. Application • Linearised, electronic temperature measurement with RTD or TC sensor.
PR 4501 DISPLAY / PROGRAMMING FRONT Functionality The simple and easily understandable PReasy menu structure and the explanatory help texts guide you effortlessly and automatically through the configuration steps, thus making the product very easy to use. Functions and configuration options are described in the section ”Configuration / operating the function keys”. Application • Communications interface for modification of operational parameters in 4114.
APPLICATIONS Input signals: Current Volt Potentio meter RTD and lin. R age Connect., wires TC 44 + + 43 * - - 42 + 41 Order separately: 5910 CJC connector. See the connection drawing on page 15. Output signals: Analogue, 0/4...20 mA and voltage 12 14 13 11 + - + 10 V 10 V - 1V 1V + + - - Supply: 33 21.6...253 VAC or 19.2...
Order codes 4114 = Universal transmitter 4501 = Display / programming front 5910 = CJC connector Electrical specifications Specifications range..................................... -20°C to +60°C Common specifications: Supply voltage, universal............................. 21.6...253 VAC, 50...60 Hz or 19.2...300 VDC Max. consumption....................................... ≤ 2.0 W Fuse.............................................................. 400 mA SB / 250 VAC Isolation voltage, test / operation......
Basic values Basic accuracy ≤ ±4 µA ≤ ±20 µV ≤ ±0.2°C ≤ ±0.1 Ω ≤ ±0.1 Ω Input type mA Volt Pt100 Linear resistance Potentiometer TC type: E, J, K, L, N, T, U TC type: R, S, W3, W5, LR TC type: B 85...200°C TC type: B 200...1820°C Temperature coefficient ≤ ±0.4 µA / °C ≤ ±2 µV / °C ≤ ±0.01°C / °C ≤ ±0.01 Ω / °C ≤ ±0.01 Ω / °C ≤ ±1°C ≤ ±0.05°C / °C ≤ ±2°C ≤ ±0.2°C / °C ≤ ±4°C ≤ ±0.4°C / °C ≤ ±2°C ≤ ±0.2°C / °C EMC immunity influence...................................... < ±0.
Cable resistance per wire (max.), RTD......... Sensor current, RTD..................................... Effect of sensor cable resistance (3- / 4-wire), RTD.......................................... Sensor error detection, RTD........................ Short circuit detection, RTD......................... TC input: 50 Ω Nom. 0.2 mA < 0.002 Ω / Ω Yes < 15 Ω Type Min. value Max.
Current output: Signal range (span)....................................... Programmable signal ranges....................... Load (max.)................................................... Load stability................................................ Sensor error detection................................. NAMUR NE 43 Upscale / Downscale.......... Output limitation: on 4...20 and 20...4 mA signals................ on 0...20 and 20...0 mA signals................ Current limit...................................
Input VOLT CURR LIN.R POTM TEMP Outside range readout (IN.LO, IN.HI): If the valid range of the A/D converter or the polynomial is exceeded Range Readout Limit IN.LO < -25 mV 0...1 V / 0.2...1 V IN.HI > 1.2 V IN.LO < -25 mV 0...10 V / 2...10 V IN.HI > 12 V IN.LO < -1.05 mA 0...20 mA / 4...20 mA IN.HI > 25.05 mA IN.LO <0Ω 0...800 Ω IN.HI > 1075 Ω IN.LO <0Ω 0...10 kΩ IN.HI < 110 kΩ IN.LO < -0.5 % IN.HI > 100.5 % IN.LO < temperature range -2°C TC / RTD IN.
CONNECTIONS Supply: 31 32 33 Inputs RTD, 2-wire RTD, 3- / 4-wire TC, internal CJC sensor Resistance, 2-wire 41 42 43 44 41 42 43 44 41 42 43 44 41 42 43 44 + - Resistance, 3- / 4-wire Potentiometer 2-wire transmitter Current 41 42 43 44 41 42 43 44 41 42 43 44 41 42 43 44 - Voltage *TC, external CJC connector 41 42 43 44 41 42 CJC 44 + + + - + * Order separately: CJC connector 5910 - - Tx Outputs Current Voltage, 1 V Voltage, 10 V 11 12 13 14 11 12 13 14 11 12 13 14
BLOCK DIAGRAM + 2-wire transmitter + - 3 2 RTD and lin. R, connection, wires 4 50.0 Potentiometer l / min VALVE 5 TC * + PT C 0. 2 mA MU X Green A /D EEPROM CP U Order separately: CJC connector 5910 44 43 CJ C 42 41 10 W 4114 Red Safety D /A 500 W 50 W Supply Supply 33 31 I+ mA V 21.6...253 VAC or 19.2...300 VDC 12 10 V mA 14 1V V I+V I V Out. Out. Out. Gnd.
CONFIGURATION / OPERATING THE FUNCTION KEYS Documentation for routing diagram. In general: When configuring the 4114, you will be guided through all parameters and you can choose the settings which fit the application. For each menu there is a scrolling help text which is automatically shown in line 3 on the display.
Signal and sensor error indication without display front Status of the unit can also be read from the red/green LED in the front of the device. Green flashing LED 13 Hz indicates normal operation. Green flashing LED 1 Hz indicates sensor error. Steady green LED indicates internal error. Steady red LED indicates fatal error. Advanced functions The unit gives access to a number of advanced functions which can be reached by answering “Yes” to the point “adv.set”.
Auto diagnosis The unit performs an advanced auto diagnosis of the internal circuits. The following possible errors can by display in the front unit 4501. CJ.ER - CJC sensor defect or CJC temperature outside range FL.ER - Flash error AO.ER - No load on the current output (only for S4...20 mA/S20...4 mA) NO.CO - Connection error IN.ER - Error levels on input TY.
ROUTING DIAGRAM Power up 50.0 3 If no key is activated for 1 minute, the display will return to the default state 1.0 without saving configuration changes. 1 Increase value / choose next parameter 2 Decrease value / choose previous parameter 3 Accept the chosen value and proceed to the next menu Hold 3 Back to previous menu / return to menu 1.0 without saving % 12.0 VOLT CURR LIN.R POTM TEMP 12 1.0 0000 9999 12 0000 3 PASSW. Txt 1 NO YES 12 2-10 0-10 1-5 0-5 0.2-1 0-1 12 @C mA rpm 12 999.9 -199.
999.9 -199.9 12 S20-4 20-4 20-0 S4-20 4-20 0-20 12 VOLT CURR 12 23mA 0/3.5mA NONE 12 4172 -328 12 4172 -328 12 3 100.0 3 CURR 3 4-20 3 23mA 3 0.0 3 150.0 3 DISP.HI Txt 14 ANA.OUT Txt 36 O.RANGE Txt 37 OUT.ERR Txt 38 10-2 10-0 5-1 5-0 1-0.2 1-0 2-10 0-10 1-5 0-5 0.2-1 0-1 12 OUT.LO Txt 41 OUT.HI Txt 42 1.3 1.2 1.3 To default state 1.0 Volt 3 0-10 3 ANA.OUT Txt 36 O.
ROUTING DIAGRAM, ADVANCED SETTINGS (ADV.SET) MEM DISP CAL SIM PASS LANG 12 2.0 In the submenu simulation (SIM) you must press 3 to return to the default state 1.0. SAVE LOAD 12 MEM 3 SAVE 3 SETUP Txt 43 MEMORY Txt 44 9 0 12 DISP 3 SETUP Txt 43 3 9 0 12 3 9 3 TAG A.OUT 12 3 A.OUT 3 CONTRA Txt 45 LIGHT Txt 46 VALVE 5 Txt 47 LINE 3 Txt 48 YES NO 12 100.0 0.0 12 YES NO 12 100.0 0.0 12 CAL 3 YES 3 SETUP Txt 43 9 A 12 2.0 3 YES 3 90.0 3 YES 3 CAL.LO Txt 49 % Txt 61 NO YES NO 12 CAL.
SCROLLING HELP TEXT IN DISPLAY LINE 3 [01] Set correct password [02] Enter advanced setup menu? [03] Select temperature input Select potentiometer input Select linear resistance input Select current input Select voltage input [04] Select 0.0-1 V input range Select 0.
Displays Programmable displays with a wide selection of inputs and outputs for display of temperature, volume and weight, etc. Feature linearisation, scaling, and difference measurement functions for programming via PReset software. Ex interfaces Interfaces for analogue and digital signals as well as HART® signals between sensors / I/P converters / frequency signals and control systems in Ex zone 0, 1 & 2 and for some devices in zone 20, 21 & 22.
www.prelectronics.fr sales@prelectronics.fr www.prelectronics.de sales@prelectronics.de www.prelectronics.es sales@prelectronics.es www.prelectronics.it sales@prelectronics.it www.prelectronics.se sales@prelectronics.se www.prelectronics.co.uk sales@prelectronics.co.uk www.prelectronics.com sales@prelectronics.com www.prelectronics.cn sales@prelectronics.cn Head office Denmark PR electronics A/S Lerbakken 10 DK-8410 Rønde www.prelectronics.com sales@prelectronics.dk tel.