2.4 OCCUPANCY SENSOR WIRING CONNECTIONS – S1 to S6
Where occupancy detection is required, a range of BlueWave sensors are
designed for use with the Universal Controller.
The preferred cable is 4-core stranded and connections will be as follows:
Note – Tamper and LED terminals on the BlueWave sensor(s) are not used.
Where more than one sensor is required for a sensor input, installation should
be as above with the exception of the wiring. To use two or more sensors
connect + & - in parallel and connect ALM contacts (ALARM) in series. The
connections on different versions of sensors may vary slightly to the drawing
below:
2.5 LIGHT LEVEL SENSOR WIRING CONNECTIONS S1 to S4
Where light level sensing is required, Universal sensors are designed for use
with the Universal controller. An inside sensor (UNI/LUX) is suitable for wall
mounting. An outside sensor (UINI/LUX/WP) is suitable for fixing in to a 20mm
conduit and may be used inside or externally. The sensor fits over the conduit
like a hat.
The preferred cable is 4-core stranded and connections will be as follows:
No more than one lux sensor can be connected to each sensor input
Universal Controller BlueWave Sensor
12V +
GND -
S + ALM (ALARM)
S - ALM (ALARM)
Universal Controller Lux Sensor (UNI/LUX or UNI./LUX/WP)
12V + (Pre-wired in RED)
GND - (Pre-wired in BLUE)
S + LUX (Pre-wired in YELLOW)
S - LUX (Pre-wired in GREEN)