User manual
10
2.6 REMOTE SWITCH WIRING CONNECTIONS – S1 to S6
Where remote switches are to be connected, two switch options exist:
a) Momentary push button / retractive switch / push switch
Note
Where more than one push switch is required on an input, simply
connect additional switches in series
.
Ranges of suitable push buttons are available, engraved to suit the
application, eg Override, Lighting etc.
b) On / Off switch (hand or key operated)
Note
Where On / Off switches are used, they will operate lighting instantly so
long as there are no PIR sensors with time delay on the system. If PIR
sensors with time delay are used, then a time delay will also apply to the On /
Off switches.
Note
Where more than one push switch is required on an input, simply
connect additional switches in series
.
Ranges of suitable on / off switches are available, engraved to suit the
application, eg On / Off etc.
2.7 REMOTE PANIC SWITCH WIRING CONNECTIONS – S5
Note
Where more than one panic switch is required, simply connect additional
switches in parallel
.
2.8 REMOTE TEMPERATURE SENSOR WIRING CONNECTIONS – S6
Universal Controller Permanent switch
S + Æ COM
S - Æ N/C
Universal Controller Push switch
S + Æ COM
S - Æ PUSH TO BREAK (N/C)
Universal Controller Panic switch
S5+ Æ COM
S5 - Æ N/O
Universal Controller Temperature sensor (UNI/RS)
S6+ Æ +
S6 - Æ -