User manual

22
Section 2 MC-III™ EXP Flow Analyzer
5.00 (127)
4.94
(125.5)
7.45
(189.3)
6.56
(16.7)
6.95
(17.65)
Figure 2.4—Remote mount on a 2-in. pole using a NuFlo hardware kit (Part No. 9A-30028004)
Hazardous Area Installations (CSA)
The CSA-approved MC-III EXP has been certied as explosion proof for Class I, Division I, Groups B, C,
and D for use in the US and Canada.
Conditions for Safe Use (CSA)
The device may be used in the presence of ammable gases and vapours with apparatus groups B, C, and
D and with temperature classes T1, T2, T3, T4, T5, and T6.
The device is certied for use in ambient temperatures in the range -40°C to 70°C and should not be used
outside this range.
Do not remove the cover unless the area is void of combustible gas and vapors.
Before removing the pipe plug to install a communications adapter, or disassembling the union nut and
blanking plug in a pre-installed communications adapter, make sure the area is nonhazardous. Reinstall
the pipe plug in accordance with the instructions in this manual.
All eld wiring must conform to the National Electrical Code, NFPA 70, Article 501-4(b) for installations
within the United States or the Canadian Electric Code for installations within Canada. State and local
wiring ordinances may also apply. All eld wiring must be rated for temperatures of 90°C or higher, and
have a wire range of 22 to 14 AWG. Terminal block screws must be tightened to a minimum torque of 5
to 7 in-lb. to secure the wiring within the terminal block. Only personnel who are experienced with eld
wiring should perform these procedures.
Do not use Teon
®
tape on threads of the union, reducer, or pipe plugs. Use of Teon
®
tape will void the
explosion-proof rating of the instrument.