User manual

13
MC-III™ EXP Flow Analyzer Section 1
LOG
TEST
SAVE
ENTER
K-FACTOR
MENU
OUTPUT
MENU
DISPLAY
MENU
DISPLAY
MENU
K-FACTOR
MENU
OUTPUT
MENU
RESET TOTAL
LOG TEST SAVE
ENTER
Day
Total
Rate
Calibrate instrument
Set flowmeter input sensitivity
Select pulse input
Enable/disable/set up 4-20 mA output
pulse output
Enter slave address
Enter baud rate
Enable/disable/set up
Set engineering units for Total readout
Set engineering units for Rate readout
Set decimal placement for both readouts
During calibration, navigates
between submenus and scrolls
through menu selections
During operation, accesses
daily volume archive
During calibration, incrementally
changes digits and decimal point
position, on/off settings
During operation, tests temperature
and system voltage
During calibration, saves
calibration settings
During operation, saves
Total to nonvolatile memory
Note: To zero the Total
readout, press the LOG (left
arrow) and SAVE (ENTER)
keys simultaneously.
Figure 1.5—MC-III EXP keypad functions
Power Supply—CSA-Approved Units
The CSA-approved MC-III EXP is shipped with either a lithium battery or an alkaline battery pack. Alter-
nately, the MC-III EXP may be powered by an external power source; in this case, the lithium battery or alka-
line battery pack provides a backup power supply, signicantly extending battery service life. A low-power
microprocessor enables the MC-III EXP to operate approximately 2 years on a single lithium battery.
Wiring diagrams for connecting an external power supply are provided in Section 2, page 19.
Power Supply—ATEX-Approved Units
The ATEX-approved MC-III EXP is shipped with a lithium battery. Alternately, the MC-III EXP may be
powered by an external power source; in this case, the lithium battery provides a backup power supply,
signicantly extending battery service life. A low-power microprocessor enables the MC-III EXP to operate
approximately 2 years on a single lithium battery.
Wiring diagrams for connecting an external power supply are provided in Section 2, page 19.