User's Manual
Table Of Contents
Receiving unit Type R302 TECHNICAL DATA
8 - 30 Vdc (~7W)
dedicated
* 10A (30Vdc)
* 10A (30Vdc)
** max 6A (30Vdc)
10A T 250V (5x20 mm)
10A T 250V (5x20 mm)
3.15A T 250V (5x20 mm)
-4°F - +158°F
Polycarbonate
IP65
(120x200x90) mm
max 2 kg
*Capacity only valid if both terminals are used for each contact.
**If the radio remote control output have been cabled by Autec, please see technical data sheet.
Power supply
Antenna
Max switching capacity of STOP contacts
Max switching capacity of SAFETY contacts
Max switching capacity of command contacts
Fuse F1 (STOP circuit)
Fuse F2 (SAFETY circuit)
Fuse F3 (POWER SUPPLY)
Working temperature
Housing
Minimum protection grade
Dimensions
Weight
LIE&LDA0
RECEIVING UNIT TYPE R302
A
B
C
D
E
F
Drilling template
A=106 mm
B=213,5 mm
A
B
The master board in this type of receiving unit is E16B10DC for configurations of up to 10
commands.
Page 7
A
cable holder (opt. plug)
D
POWER light
B
identification plate
E
ENABLE light
C
data technical plate
F
antenna
E16B10DC
F1
F2
F3
F1
STOP circuit protection
fuse
F2
SAFETY circuit
protection fuse
F3
POWER SUPPLY
protection fuse