Warnings for installation
At end of installation
AUTEC - Dynamic Series
LIUDYN2AB0-01_eng.fm User manual
27
The power supply of the receiving unit must have a switch that allows power sup-
ply disconnection during installation, wiring and/or maintenance operations. Con-
nect the receiving unit immediately downstream of the machine main switch or of
the electrical panel main switch.
Pay special attention to the currents flowing in outputs SAF_1_OUT,
SAF_2_OUT, STOP_1_OUT and STOP_2_OUT: they shall not exceed the max-
imum permitted values (see paragraph 8.2).
The current of STOP outputs is interrupted at regular intervals for approx. 1 ms
every 100 ms. If STOP outputs are used to power electronic devices, check that
they are compatible with this recurring interruption (use suitable filters if neces-
sary).
9.5 At end of installation
Make sure that during installation the safety mechanisms on the radio remote
control and/or in the machine have not been made ineffective by possible proce-
dures carried out.
9.6 Testing
After installation and wiring, test the system “machine+radio remote control”, and
check that the operations carried out correspond exactly to the commands sent
(in particular check the STOP command).
The installer must check and complete the "Technical Data Sheet" in all its parts,
adding the date the system has been put into service, his stamp and signature.
In case of malfunction, disable the system “machine+radio remote control” until
the problem has been completely solved.