Malfunction signalled by the Receiving Unit
AUTEC - Dynamic Plus series
10 Malfunction signalled by the Receiving Unit
The table below lists malfunctions highlighted by signals on the Receiving Unit.
If the problem persists after attempting the suggested solution, contact the support service
of the Machine Manufacturer.
Signals Possible reason Solutions
The POWER LED is o󰓐. The Receiving Unit is o󰘯.
Make sure that the power supply
protection fuse is intact (fuse F9).
Correctly plug in the connecting plug
and power on the Receiving Unit.
Error on output STP_1.
Make sure that the protection fuse for
output STP_1 is intact (fuse F8).
Correctly plug in the connecting plug.
Make sure that output STP_1 is wired
correctly.
Error on STP_2 output.
Make sure that the protection fuse for
output STP_2 is intact (fuse F7).
Correctly plug in the connecting plug.
Make sure that output STP_2 is wired
correctly.
Error on output SAF_1.
Make sure that the protection fuse for
output SAF_1 is intact (fuse F6).
Correctly plug in the connecting plug.
Make sure that output SAF_1 is wired
correctly.
Error on output SAF_2.
Make sure that the protection fuse for
output SAF_2 is intact (fuse F5).
Correctly plug in the connecting plug.
Make sure that output SAF_2 is wired
correctly.
The STATUS LED blinks
slowly.
Over-voltage on power
supply.
Make sure that the Receiving Unit
power supply is within the voltage limits
provided in the technical data.