Instruction Manual
www.austin-hughes.comUM-X-600-ISM-Q214V2 P.23
Using dip switch no. 1, 2, 3, 4, 5, 6 & 8 to setup each FAN unit level as below :
Cascaded
FAN unit
Dip switch no.
1234568
1st level Fan Unit On On On On On On Off
2nd level Fan Unit Off On On On On On Off
ON
OFF
Dip switch 7
Enable On
Disable Off
Using dip switch no. 7 to setup each FAN unit audio alarm as below :
If enable the audio alarm, the buzzer will
sound when the outside temperature is
over the preset alarm temperature.
InfraBox X-2000
OUT
OUT
1st level Fan unit
LINK
LINK
2nd ( last ) level Fan unit
Cat 5 / 6 cable
Up to 20M
Under an InfraSolution X network, each InfraBox supports InfraCool remote fan unit x 2 in a daisy chain.
Each fan unit comes with TEMP. sensor port x 1
Max. daisy chain distance from InfraBox to the 2nd fan unit up to 40M
Please visit below link to select desired Fan unit models
http://www.austin-hughes.com/solutions/intelligent-fan-units.html#RMounted
< 3.2 > Fan Unit