Instruction Manual
www.austin-hughes.comUM-ICM-02-Q215V1 P.18
< 2.5 > Daisy Chain Connection
Using the dip switch no. 1, 2, 3, 4, 5, 6 & 8 to setup each FAN unit level as below :
Cascaded FAN units Dip switch no.
1234568
1st level
Master IP Fan Unit Model On On On On On On Off
2nd level Remote Fan Unit Model Off On On On On On Off
3rd level Remote Fan Unit Model On Off On On On On Off
4th level Remote Fan Unit Model Off Off On On On On Off
5th level Remote Fan Unit Model On On Off On On On Off
6th level Remote Fan Unit Model Off On Off On On On Off
7th level Remote Fan Unit Model On Off Off On On On Off
8th level Remote Fan Unit Model Off Off Off On On On Off
9th level Remote Fan Unit Model On On On Off On On Off
10th level Remote Fan Unit Model Off On On Off On On Off
11th level Remote Fan Unit Model On Off On Off On On Off
12th level Remote Fan Unit Model Off Off On Off On On Off
13th level Remote Fan Unit Model On On Off Off On On Off
14th level Remote Fan Unit Model Off On Off Off On On Off
15th level Remote Fan Unit Model On Off Off Off On On Off
16th level Remote Fan Unit Model Off Off Off Off On On Off
Daisy chain level setting
ON
OFF
** No. 7 dip switch only for audio alarm setting
Steps :
■ Only Master IP fan unit built-in IP remote access module.
■ Master IP fan unit MUST be set on the 1st daisy chain level according to the table below.
■ For the 2nd - 16th levels ( remote fan unit models ), please make the level setting according to the table below.
■ For the cabling connection, please refer to the next page.