P.21
< 3.1 > PDU
Master EC Box
Alarm
Beacon
- Lamp -12Smoke / Shock
PDUT1 T2 Fan
ON DIP
18765432
Box Level
Power
12VDC
LAN Out
341
Door
2
T1 T2
- Water -12
For details about PDU level setting, please refer to IPM-03 user manual < 3.1 > :
http://www.austin-hughes.com/support/usermanual/infrapower/UM-IPM-03.pdf
Please visit below link to select desired PDU & download the PDU drawing & speci cations.
http://www.austin-hughes.com/solutions/intelligent-kWh-pdu.html#Single_Phase
1st level
PDU meter
4th ( last ) level
PDU meter
3rd level
PDU meter
2nd level
PDU meter
Cat 5 / 6 cable
Up to 20M
Cat 5 / 6 cable
Up to 20M
Cat 5 / 6 cable Up to 20M
Cat 5 / 6 cable
Up to 20M
Step 1 - Press the & button to display no.9 and press to con rm
Step 2 - Press the & button to PDU ID and press to con rm
Step 3 - In display 9.1, Press the & button to select PDU level no. & press to con rm
Step 4 - Press to exit
PDU level setting :
Part III. PDU / Fan Unit Installation & Speci cations
Under an InfraGuard network, each EC Box supports InfraPower intelligent PDU x 4 in a daisy chain.
Each PDU comes with Temp. & Humid. sensor port x 2
W series : monitored PDU
WS series : switched PDU
WSi series : outlet level measurement switched PDU
Max. daisy chain distance from EC box to the 4th PDU up to 80M