Technical data

Step-by-step procedure for configuration of the photovoltaic generator with Aurora Designer
Step 1 General Data entry
Selection of language
Selection of PV panels brand and model (one model only)
Selection of inverter models
Selection of mounting type
Setting up minimum ambient temperature (also used as minimum cell
temperature to calculate string voltages)
Setting up maximum ambient temperature (maximum cell temperature at
which the string voltages are assessed; it is assessed taking into consideration
the type of mounting selected)
Setting up the panel Derating Coefficient: what does the panel Derating
Coefficient take into account?
Maximum cell temperature: related to assembly type -max
ambient temperature
Max cell temperature= max ambient temperature+ ΔT
Solar tracker: ΔT=25°C
Mounted on structure: ΔT=30°C
Roof mounted: ΔT=35°C
Panel derating coefficient(PDC)
Estimate of losses in DC section of system :
Resistive losses in cables/fuses/disconnectors
Power losses due to mismatching in the photovoltaic generator
Losses connected to dirt/dust on the photovoltaic generator
Decay of the panel performance
Derating of the power available from the photovoltaic generator due
to non-optimal conditions of installation
nomPpvinvPdcPDC ,/,
Dimensioning systems with Power-One inverters