Operator`s manual

Installation and Operator’s Manual Page 58 of 62
(PVI-2000-OUTD-UK
Rev: 1.0)
Description
Value
PVI-2000-OUTD-
UK
Nominal input voltage 360Vdc
Minimum input voltage to
connect to the grid
200Vdc
“Absolute Maximum Rating”
for input voltage
600Vdc
Input voltage, MPPT operating
range
90Vdc to 580Vdc
Input voltage, MPPT range at
full power
220Vdc to 530Vdc
Max. short circuit current 12Adc
Max. operating input current 10Adc
Max. input power 2200 W
PV Ground fault protection
Ground fault detection and shut off of
utility-interactive inverter
Array configuration One array
As stated above, AURORA performs an analysis of the photovoltaic field and
constantly researches the max. input Dc power point. This process is called MPPT
(Maximum Power Point Tracking).
NOTE: If the input current supplied by the photovoltaic field connected
to the inverter is above the max. value and the input voltage is within the
allowed range, the inverter is not damaged.