Up to 31 AURORA inverters can be connected on the same RS-485 line. The
maximum recommend RS-485 cable length is 1300 yards (1200 m).
In case multiple inverters are daisy-chained to the same RS-485 line, then the last
unit must be terminated by changing the position of the dip-switch shown in
Fig.19 from OFF to ON. The default position of the switch is OFF. Also, each
unit must have a different address. See par. 6.5 to change the addresses.
In order for the RS485 communication line to perform the best, Power-One
recommends to connect its PVI-RS232485 adapter before the first unit of the
daisy-chain (see fig. 17 for details)
Equivalent devices may also be used for the same purpose, but they have not been
tested therefore
Power-One can
n
ot grant the right functionalities.
Please also not
e
that ordinary commercial adapters may need additional impedance
termination. Aurora PVI-RS232485 adapter DOES NOT.
The following diagram shows how to connect multiple units on the same RS-485
bus.