most probably a temporary reduction of the insulation resistance
(for example the water seepage on the modules caused by
condensation). It is recommended to call qualified personnel to
perform an inspection of the installation in case this disconnection
events are recurrent. If the fault cannot be reset, that is causing a
ground fault or there is some other insulation breakdown.
If the signal cannot be reset, insulate AURORA on both Dc and
Ac sides so as to reach a safe condition; then contact an
authorized center for repairing the fault.
G
Y
R
5) Malfunction-Fault Signal
Every time AURORA check system detects an operative
malfunction or fault, the yellow LED comes on and a message
showing the type of problem found appears on the LCD.
G
Y
R
6) RS-485 Address Setting Signal
During installation, the yellow LED will flash until the address is
confirmed. For further information about setting the address, refer
to chapter 6.3.
G
Y
R
7) AC grid voltage missing
When the system is normally activated and operating, if for any
reason there is a permanent loss of mains the inverter will signal
this fault status with the yellow LED on and green LED blinking.
This fault may be caused by a defective automatic circuit breaker
or a fault in the AC wiring to the inverter or a system fault in the
AC network.