Owner manual
20.2 Programming the logic board
The type of seating – limit or torque seating – (switch S1-2 and switch S3-2, fig
-
ure AC) must be determined by the valve manufacturer.
.
Set desired programming according to table 4 at the switch S2-2.
35
Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
Operation instructions with actuator controls AUMA MATIC AM 01.1 / AM 02.1
Position 1:
Limit
seating
in end position OPEN
Position 2:
Torque
seating
in end position OPEN
Position 1:
Limit
seating
in end position CLOSED
Position 2:
Torque
seating
in end position CLOSED
S3-2
S1-2
S2-2
Figure AC: Logic board A2
DIP switch S2-2
Programming
(ON = pressed)
Direction CLOSE Direction OPEN
Self-retaining REMOTE
Push-to-run operation REMOTE
Self-retaining LOCAL
Push-to-run operation LOCAL
Blinker transmitter (option)
activated
deactivated
Torque fault: Torque switch trip-
ping (in mid-travel) contained in
collective fault signal
included not included
Table 4