User`s manual

Chapter 3 Function
3-46
3
Reset
The function resets the measurement value.
At the time of making a peak measurement, valley measurement, or peak-to-peak
measurement with external multi input (MI), the measurement value kept on hold
at the desired timing can be reset.
Input a specified pulse width as multi input.
The pulse width can be input into the high-function type through a communications
command.
For details,
refer to "2-4 Timing Chart".
All judgment outputs will be turned OFF when
Reset
is executed. This
function can be applied to judge each measurement object for peak, valley, o
r
peak-to-peak measurements.
If “Reset” is executed, the system will be in a data unfixed status, analog output
will be set to a preset fix value (21.6 [mA] and +11.000 [V]), and all the
judgment outputs will be OFF.
If Reset ON is executed by a communications command, the memory contents
will be cleared to zero after Reset is executed.
The sensor head does not save setting changes made over the multi-input line.
Save the settings over the multi-input line, through the panel, with the
communications command, or with the operation of the console if the settings
need to be maintained after the system is turned OFF.
Setting Procedure
1
Press the [UP]/[ENTER] keys together
while in Run mode.
Reset will be executed.