Technical data

Chapter 4 Deployment Manual VIPA System 300S SPEED7
4-24 HB140E - CP - RE_343-1EX71 - Rev. 09/46
The slot assignment of the SPEED-Bus modules and the parameterization
of the in-/output periphery happens via a virtual Profibus DP master
system. For this, place as last module a DP master (342-5DA02 V5.0) with
master system.
For the employment of the System 300S modules at the SPEED-Bus the
inclusion of the System 300S modules into the hardware catalog via the
GSD-file SPEEDBUS.GSD from VIPA is required.
After the installation of the SPEEDBUS.GSD you may locate at
Profibus DP / Additional field devices / I/O / VIPA_SPEEDBUS
the DP slave system VIPA_SPEEDBUS.
Now include for the CPU and every
module at the SPEED-Bus a slave
system "VIPA_SPEEDBUS".
Set as Profibus address the slot no. (100...116) of the module and place
the according module from the hardware catalog of VIPA_SPEEDBUS to
slot 0 of the slave system.
DP master system for SPEED-Bus modules
(100) VIPA
VIPA_SPEEDBUS
Order no.
31xS - SPEED7-CPU
SPEEDb us
Slot
0
(104) VIPA
VIPA_SPEEDBUS
Order no..
331-1DA70 - AI
SPEED bus
Slot
0
The according module is to be taken from the
hardware catalog to slot 0 of VIPA_SPEEDBUS.
101105 102103104
Slot:
100
(101) VIPA
VIPA_SPEEDBUS
Order no.
321-1BH70 - DI
SPEEDb us
Slot
0
(103) VIPA
VIPA_SPEEDBUS
Order no.
343-1EX71 - Ethern
SPEEDb us
Slot
0
(105) VIPA
VIPA_SPEEDBUS
Order no.
323-1BH70 - DIO
SPEEDbus
Slot
0
Setting of the slot
via Profibus address
(102) VIPA
VIPA_SPEEDBUS
Order no.
322-1BH70 - DO
SPEEDb us
Slot
0
Ethernet-
Network
with Siemens
NetPro
Module
CPU 318-2
DP
MPI/DP
IM 360
DI
DO
DIO
AI
AO
343-1EX11
343-1EX11
343-1EX11
Standard bus
Slot
1
2
X2
X1
3
4
5
6
7
8
9
10
11
Standard bus (serial)SPEED-Bus (parallel)
CPU 31xS
DIDO
Ethernet
CP 343
DI DO DIO AI AOAIDIO
Ethernet PG/OP
CP343
(CPU 31xSN/NET)
Module
IM 361
CP 342-5
Standard bus
Slot
1
2
3
4
5
6
7
8
9
10
11
Note!
Let with the CPs or DP master (also virtual SPEED-Bus master) at
options
the attitude "Save configuration data on the CPU" activated!
Project engineering
each SPEED-Bus
module in a virtual
master system