Technical data

Manual VIPA System 300S SPEED7 Chapter 4 Deployment
HB140E - CP - RE_343-1EX71 - Rev. 09/46 4-19
Hardware configuration
The project engineering of the Ethernet CP 343S-NET - SPEED-Bus takes
place at the Siemens hardware configurator and is divided into 2 parts:
Project engineering and connecting at the standard bus as Siemens
CP 343-1 (343-1EX11)
Project engineering as single VIPA_SPEEDBUS DP slave with CP 343-
1EX71 at a virtually DP master (SPEEDBUS.GSD necessary).
For the deployment of the Ethernet CP 343S-NET at the SPEED-Bus, the
inclusion via the GSD-file from VIPA in the hardware catalog is required.
Standard bus
virtual DP master for CPU
and every SPEEDbus module
real modules
at the standard bus
CPs resp. DP master
at SPEED-Bus as
343-1EX11 resp. 342-5DA02
(100) VIPA
VIPA_SPEEDBUS
Order no.
CPU at slot 100
SPEEDbus
Slot
0
(n) VIPA
VIPA_SPEEDBUS
Order no.
Module at slot n
SPEEDbus
Slot
0
...
Module
CPU 318-2
DP
MPI/DP
342-5DA02 V5.0
Slot
1
2
X2
X1
3
343-1EX11
(Ethernet PG/OP)
343-1EX11
(only CPU 31xSN)
To be compatible with the Siemens SIMATIC manager, you have to
execute the following steps:
Start the hardware configurator from Siemens and include the
SPEEDBUS.GSD for SPEED7 from VIPA.
Configure CPU 318-2DP (6ES7 318-2AJ00-0AB0/V3.0) from
Siemens. Configure a possibly existing internal DP master of your
SPEED7-CPU via the internal DP master of the CPU 318-2DP.
Leave
MPI/DP of the CPU 318-2DP in MPI mode. The Profibus
mode is not supported.
Starting with slot 4, place the System 300 modules in the plugged
sequence.
For the internal Ethernet PG/OP channel that every SPEED7-CPU
includes, you have to configure a Siemens CP 343-1 (343-1EX11)
always
as 1. module below the really plugged modules.
If exists the integrated CP 343 of the CPU 31xSN/NET is also
configured as CP 343-1 (343-1EX11) but always below the before
configured PG/OP channel. Else start here to configure and
connect every Ethernet CP 343S-NET - SPEED-Bus as Siemens
CP 343-1 (343-1EX11).
For the SPEED-Bus you always include, connect and parameterize
to the
operating mode DP master the DP master CP 342-5
(342-5DA02 V5.0) as last module. To this master system you
assign every SPEED-Bus module as VIPA_SPEEDBUS slave.
Here the Profibus address corresponds to the slot no. Beginning
with 100 for the CPU. Place on slot 0 of every slave the assigned
module and alter the parameters if needed.
Let with the CPs or DP master (also virtual SPEED-Bus master) at
options the attitude "Save configuration data on the CPU"
activated!
Overview
Fast introduction