Configure the internal PG/OP channel directly under the really plugged
modules as virtual CP 343-1 (343-1EX11) from Siemens and set IP
address, subnet mask and gateway at CP properties.
If used always configure as 2. CP the internal CP 343 of a CPU
31xSN/NET as CP 343-1 (343-1EX11) by setting another IP address,
subnet mask and gateway.
Else configure as 2. CP the Ethernet CP 343S-NET - SPEED-Bus as
CP 343-1 (343-1EX11) by setting another IP address, subnet mask and
gateway.
Please always assign valid IP parameters when using CPs.
A Siemens CP 342-5 (342-5DA02 V5.0) operating as DP master should
be set and connected as last module.
To this master system you assign every SPEED-Bus module as
VIPA_SPEEDBUS slave. Here the Profibus address corresponds to the
slot no. Beginning with 100 for the CPU. Place on slot 0 of every slave
the assigned module and alter the parameters if needed.
This is the end of the project. After transmission to the CPU the CP can be
accessed using the IP address and subnet mask of the project.
For deployment of the ISO transport connections they must be enabled in
the Ethernet properties of the CP at the project above.
Here there is the possibility to assign the CP to a MAC address. With each
start-up of the CPU the new MAC address is transferred to the CP.
The link-up between the stations happens with the graphical interface
NetPro. Start NetPro by clicking on a network in your project res. on
connections in the CPU directory.
Connections
[5]
Deployment of
ISO transport
connections
Configure
connections with