Technical data

Manual VIPA System 300S SPEED7 Chapter 4 Deployment
HB140E - CP - RE_343-1EX71 - Rev. 09/46 4-15
You get valid IP address parameters from your system administrator. For
the assignment of the IP address parameters such as IP address, Subnet
mask etc. you have the following possibilities:
Online using Siemens SIMATIC manager via "Assign Ethernet Address"
(at least CP-Firmware 1.7.4)
With a project with IP address and IP parameters transferred via MMC
or MPI to the CPU. After a reboot of the CPU and after switching the
PG/PC interface to "TCP/IP... RFC1006" you may now configure your
CPU online via the CP.
Please regard this functionality is available with CP firmware version 1.7.4
and up. In the following the proceeding with the Siemens SIMATIC
manager starting with version V 5.3 & SP3 is described:
Start the Siemens SIMATIC manager.
Switch to "TCP/IP... RFC1006" using Options > Set PG/PC interface.
The dialog for initialization of a station opens by PLC > Edit Ethernet
Node
.
To get the stations and their MAC address, use the [Browse] button or
type in the MAC Address. The Mac address can be found at a label
beneath the front flap of the CP.
Choose if necessary the known MAC address of the list of found
stations.
Either type in the IP configuration like IP address, subnet mask and
gateway. Or your station is automatically provided with IP parameters by
means of a DHCP server. Depending of the chosen option the DHCP
server is to be supplied with MAC address, equipment name or client ID.
The client ID is a numerical order of max. 63 characters. The following
characters are allowed: "hyphen", 0-9, a-z, A-Z
Confirm with [Assign ...].
Directly after the assignment the CP is online reachable using the set IP
parameters.
Start Siemens SIMATIC manager with new project.
Place a new System 300 station with Insert > Station > SIMATIC 300
station
Activate the station "SIMATIC 300" and open the hardware configurator
by clicking on "Hardware".
Configure a rack (SIMATIC 300 \ Rack-300 \ Profile rail).
Engineer in deputy of your CPU 31xS the Siemens CPU 318-2DP with
the order no. 6ES7 318-2AJ00-0AB0 V3.0 which is to be found at
SIMATIC 300 \ CPU 300 \ CPU 318-2 \ 6ES7 318-2AJ00-0AB0. If
needed, parameterize the CPU 318-2DP.
Place the System 300 modules in plugged sequence starting with slot 4.
continued ...
Assign IP
parameters
Address
assignment with
"Assign Ethernet
Address"
Address
assignment with
project