Technical data

Chapter 4 Deployment Manual VIPA System 300S SPEED7
4-14 HB140E - CP - RE_343-1EX71 - Rev. 09/46
Fast introduction
At the first start-up respectively at an over all reset the Ethernet CP 343S-
NET - SPEED-Bus does not have
any IP address. The CP may only be
contacted by its MAC address. IP address parameters may be assigned to
the CP by means of the MAC address, which may be found on a label
beneath its front flap. The assignment takes place directly via the hardware
configuration of the Siemens SIMATIC manager. For the project
engineering of an Ethernet CP 343S-NET - SPEED-Bus please follow this
approach:
Assembly and commissioning
Hardware configuration (Inclusion of CP in CPU)
CP project engineering via NetPro (connection to Ethernet)
PLC programming via user application (connection to PLC)
Transfer of the complete project to the CPU
To be compatible to the Siemens SIMATIC manager, the CPU 31xS from VIPA has to
be configured as
CPU 318-2DP (6ES7 318-2AJ00-0AB0)
The Ethernet CP 343S-NET - SPEED-Bus is configured and connected as virtual
module after the really plugged modules and below the PG/OP channel at the
standard bus as Siemens CP 343-1 (343-1EX11). In addition the Ethernet CP 343S-NET
- SPEED-Bus is to be placed as single VIPA_SPEEDBUS DP slave at a virtually DP
master.
Install your System 300S with a CPU 31xS and an Ethernet CP 343S-
NET - SPEED-Bus.
Wire the system by connecting cables for voltage supply, signals and
Ethernet. A detailed description is to be found in the chapter "Assembly
and installation guidelines".
Switch Power ON. After a short boot time, the CP is in idle mode.
At the first start-up res. after an overall reset of the CPU the Ethernet
CP 343S-NET - SPEED-Bus does not have an IP address. For control
purposes you may now reach the CP via the MAC address. The MAC
address is to be found beneath the front flap at a small label on the
module.
Overview
Note
Assembly and
commissioning