Technical data

Chapter 1 Basics Manual VIPA System 300S SPEED7
1-6 HB140E - CP - RE_343-1EX71 - Rev. 09/46
Wiring by means of spring pressure connections (CageClamps) at the
front connector
Core cross-section 0.08...2.5mm
2
Total isolation of the wiring at module change
Potential separation of all modules to the backplane bus
ESD/Burst acc. IEC 61000-4-2/IEC 61000-4-4 (up to level 3)
Shock resistance acc. IEC 60068-2-6 / IEC 60068-2-27 (1G/12G)
Operating temperature: 0 ... +60°C
Storage temperature: -25 ... +70°C
Relative humidity: 5 ... 95% without condensation
Ventilation by means of a fan is not required
Available lengths of the profile rail in mm: 160, 482, 530, 830 and 2000
Dimensions of the basic enclosure:
1tier width: (HxWxD) in mm: 40x125x120
2tier width: (HxWxD) in mm: 80x125x120
Modules and CPUs of the System 300 from VIPA and Siemens may be
used at the "Standard" bus as a mixed configuration.
The project engineering takes place in WinPLC7 from VIPA or in the
hardware configurator from Siemens.
The SPEED7 CPUs from VIPA are instruction compatible to the
programming language STEP
®
7 from Siemens and may be programmed
via WinPLC7 from VIPA or via the Siemens SIMATIC manager.
Here the instruction set of the S7-400 from Siemens is used.
Note!
Please do always use the CPU 318-2DP (6ES7 318-2AJ00-0AB0/V3.0)
from Siemens of the hardware catalog to project a SPEED7-CPU with
SPEED-Bus from VIPA. For the project engineering, a thorough
knowledge of the Siemens SIMATIC manager and the hardware
configurator from Siemens is required!
Every CPU res. bus coupler comes with an integrated power supply. The
power supply has to be supplied with DC 24V. By means of the supply
voltage, the bus coupler electronic is supplied as well as the connected
modules via backplane bus. Please regard that the integrated power supply
may supply the backplane bus the backplane bus (SPEED-Bus and
Standard-Bus) depending on the CPU with a sum with max. 5A.
The power supply is protected against inverse polarity and overcurrent.
Every SPEED-Bus rail has a plug-in option for an external power supply.
This allows you to raise the maximum current at the backplane bus for
5.5A.
Operation Security
Environmental
conditions
Dimensions/
Weight
Compatibility
Integrated
power supply