Specifications

VA4Z XM S
AUDIO SYSTEMS
V-EVAC SYSTEM
17
VA4Z S VA4Z SU
Slave module for Public Address
and evacuation compliant with
the EN60849 standard for small to
medium installations
• Matrix composed of 4 audio
inputs, 1 microphone input for
emergency messages, 4 outputs
for 4 independent zones.
Optional switching module
Maintains the emergency
microphone facility to the VA4Z
In case of failure of one or more
master or slave units, it will
automatically connect one PSS
microphone station directly to
amplifier input, allowing users to
make an all-call announcement
For each zone it allows a+b wiring
on same amplifier: when two
loudspeaker lines are used in
a zone, they can be connected
to the same amplifier and this
module will ensure the separate
line surveillance, in compliance
with the EN60849 and BS5839 part
8 standards
Slave module for Public Address
audio system
• It has the same features as
VA4ZS and, in addition, it
features automatic gain control:
the sensing microphone
(PABFMP) can be connected to
one of the audio inputs
• It will allow VA4Z to carry out an
intelligent measure of the noise
level, adapting the gain of the
corresponding zones
482
44
PSS DT
Paging microphone console
PSS24DT Code 27835
PSS96DT Code 31208
PSM8 Code 29972
PMM-JB Code 29973
VA4Z S VA4Z SU VA4Z XMS
Code 27828 29415
0 dB Inputs/Outputs
Audio input impedance 10Kohm
Input sensitivity 0dB
Audio output impedance 50Kohm
Output levels 0dB
Maximum input/output level +14dBu
Audio band from 10Hz to 22kHz
Sampling 48kHz 24 bits
Distortion da 0.02% a 1kHz
Output noise <-84dBu Lin, <-88dBu A-weighted
Dynamic output >98dBu Lin, >102dBu A-weighted
100 V Inputs/Outputs
Maximum power per channel 500W per ogni VA8Z
Amplifier gain measurement 1kHz 18kHz
Line impedance measurement 100V 18kHz
Ground fault measurement 12 VDC 0 a 10 Mohms
Digital audio messages 4 messages, total length 2 mins 11 secs
Bandwidth 8kHz
Sampling 16kHz 16 bits
Alarm input/output contacts
Alarm inputs (24V -72V activation) 4
Output contacts (error due to lack 4
of the line file component)
Contact input 1powerfaultorbatterybackupfault
Output contact (on/off control) 1
Serial connections
Connection to PSS849 1 RS485
Connections to message console 2 RS232
Connections to PC 2 RS232
Colour Grey RAL7016 2 RU 19”
Dimensions (WxHxD) 430x88x230mm