Specifications
54 555554
Actuators
BUILDING
UNIVERSAL 8 IN - 8 OUT C-LOAD
MULTIFUNCTIONAL 4 IN / 4 OUT - MULTIFUNCTIONAL 8 IN / 8 OUT
The DIN RAIL 8 Input / 8 Output Module IO88B02KNX-C is an EIB/KNX DIN rail mounting device useful to interface commands
(e.g. push buttons) or loads (e.g. lamps) for any kind of applications. The device is equipped with 8 binary inputs (clean con-
as output channels to drive LEDs in synoptic monitoring panels.
Relay from 5 to 8 are equipped with manual command and can be switched manually.
Device is intended to be installed on DIN rail.
The products IO44E01KNX & IO88E01KNX are an EIB/KNX DIN rail mounting devices useful to interface commands (e.g. push buttons)
or loads (e.g. lamps) for any kind of applications. The devices are equipped with 4 or 8 binary inputs (clean contacts) and 4 or 8 binary relay
ORDER CODE
ORDER CODES
TECHNICAL FEATURES
TECHNICAL FEATURES
Universal 8 IN - 8 OUT C-Load
Multifunctional 4 IN / 4 OUT
Multifunctional 8 IN / 8 OUT
IO88B02KNX-C
IO44E01KNX
IO88E01KNX
Dimensions
(W x H x D): 72 x 90 x 58 mm
Mounting width: 4 DIN modules (1 SU=18mm)
Mounting
Bus Line: 2 Terminal of bus connection , Max section 0,8mm²
Outputs: 2 screw terminals by channel max. section 4 mm²
Inputs: 3 screw terminals every 2 inputs, max. section 4 mm²
Supply
From Bus KNX 21..30 V DC SELV
Dimensions(W x H x D): 72 x 90 x 58 mm
Mounting width: 4 (1 SU=18mm)
Mounting
Bus Line: 2 Terminal of bus connection , Max section 0,8mm²
Outputs: 2 screw terminals for channel Max. 4 mm²
Inputs: 3 screw terminals every 2 inputs, Max. 4 mm²
Supply
From KNX bus 21..30 V DC SELV
Features
4 or 8 binary inputs for clean contacts
Max length 30m twisted cables
Features
8 binary inputs for potential-free contacts
Max length 30m twisted cables
Features relay outputs
Resistive: 16 A Max
Incandescent lamps: 10 A Max
Motors and motor reductors: 10 A Max
Fluorescent lighting transformer. Electronic: 6 A Max
Fluorescent lamps (Max. 140 µ) 700W Max
Features relay outputs
Resistive Loads: 16 A Max - 230 VAC
Incandescent lamps:10 A Max
Motors : 10 A Max
Fluorescent lighting transformer 2 A Max
Fluorescent lamps: use always an external counter
ACTUATORS - INTERFACE - PRESENCE SENSOR KNX
3 X 300W DIMMER MODULE
The 3 channel Dimmer Module is designed to drive dimmerable lighting with KNX bus and allow dimming of incandescent
and halogen loads of 230V, BT and TBT. The product can control one (900 W), two (600+300 W) or three (3x300 W) independent
lighting circuits.Device is intended to be installed on DIN rail.
ORDER CODE
TECHNICAL FEATURES
3 x 300W Dimmer Module
DM03B02KNX
Dimensions
(H x W x D) 85 x 105 x 60 mm
Mounting
Width 6 mod. DIN (um 18mm)
Connections
Bus line: 2 bus connection terminals, section 0,8 mm²
Outputs: 2 plug-in terminals for each channel section conductors
from 0.75 mm² to 2.5 mm²
Supply
From the KNX bus and power supply 230 V 50/60 Hz
3 power outputs with the following characteristics
Power: 20 W to 300 W output with the possibility
of coupling
between them.
Power consumption without load 5 W
Control elements
1 button to set the maximum value of brightness
Max. or Min.
1 button for manual control of each output
Indicators
1 red LED for programming ETS
UNIVERSAL MODULE 4 / 8 OUT
The DIN RAIL 4 and 8 Output Modules BO04A01KNX - BO08A01KNX are an EIB/KNX DIN rail mounting devices useful to
interface loads (e.g. lamps) for any kind of applications.
model BO08A01KNX. Device is intended to be installed on DIN rail.
ORDER CODES
TECHNICAL FEATURES
Universal Module 4 OUT
Universal Module 8 OUT
BO04A01KNX
BO08A01KNX
Dimensions
(W x H x D): 72 x 90 x 58 mm
Mounting
4 modules DIN
Connection
Outputs: 2 screw connectors by channel max 4mm2
Supply
From KNX bus 21..30 V DC SELV
Features relay outputs:
Resistivei: max 16 A
Incandescent Lamps: max 10 A
Motors and motor reductors : max 10 A
Fluorescent lighting transformer electronic: max 4 A
Fluorescent lamps: (max 140 µF) max 3 A (700W)
UNIVERSAL MODULE 12 OUT
BO12A01KNX is a Din Rail 12 output 16 A actuator, it can be used to control up to 12 independent loads / lights , control
up to 6 independent blind / roller shutters with mechanical end position. This device is intended to be installed on DIN rail.
ORDER CODES
TECHNICAL FEATURES
Universal Module 12 OUT
BO12A01KNX
Dimensions
(W x H x D): 90 x 159 x 58 mm
Mounting
9 modules DIN
Supply
From KNX bus 21..32 V DC SELV
Current Consumption <10mA
Features relay outputs:
Resistive: max 16 A
Incandescent Lamps: max 10 A
Motors and motoreductor : max 10 A
Fluorescent lighting transformer electronic: max 4 A
Fluorescent lamps: (max 140 µF) max 3 A (700W)
UNIVERSAL 4 IN - 4 OUT C-LOAD
The DIN RAIL 4 Input / 4 Output Modules IO44B02KNX-C is an EIB/KNX DIN rail mounting device useful to interface com-
mands (e.g. push buttons) or loads (e.g. lamps) for any kind of applications.
The device is equipped with 4 binary inputs (clean contacts) and 4 relay outputs suitable for capacitive loads (-C code).
include switching function, scenarios, logic functions.
2 speeds. Devices are intended to be installed on DIN rail.
ORDER CODE
TECHNICAL FEATURES
Universal 4 IN / 4 OUT C-Load
IO44B02KNX-C
Dimensions
(W x H x D): 72 x 90 x 58 mm
Mounting width: 4 DIN modules (1 SU=18 mm)
Connection
Bus line, bus connecting terminal, wire max section 0,8mm²
Outputs: 2 screw connectors by channel max section 4 mm²
Inputs: 3 connectors every 2 inputs, max. section 4 mm²
Power Supply
From KNX Bus 21..30 V DC SELV
Features
4 binary inputs for clean contacts
Max length 30m twisted cables
Features relay outputs
Resistive: 16 A Max
Incandescent lamps: 10 A Max
Motors and motor reductors: 10 A Max
Fluorescent lighting transformer. Electronic: 6 A Max
Fluorescent lamps (Max. 140 µ) (700W Max)