Instruction manual

40
off by the flue gas sensor temperature decreases for 25% within 15 minutes, the boiler is
switched off.
The STB is started Residual warmth off-take is stopped, if the boiler temperature
is < 85°C. If, then, the boiler temperature increases to > 86°C,
usage of residual warmth starts again.
Function of switching contact When the boiler is switched on: WK/AK is closed
When the boiler is switched off and flue gas temperature is
<100°C: WK/RK is closed
Error of CPU All relays are turned off by Hardware Watchdog
Antifreeze protection When the boiler is switched off and the temperature is < 7°C:
Start of connecting pump, Y1 a Y2 = 100%.
If boiler temperature increases to > 8°C, connecting pump is
stopped.
Y1=0%, Y2= 100%.
Protection of flue gas fan and
of flue gas sensor against
overheating
Flue gas temperature > 350°C, flue gas fan is stopped
Flue gas temperature < 299°C, flue gas fan is switched on
Short circuit of the „+“ button Button of regulator does not react, even not to significant
pressure
Enter function (Menu) After safety time, the menu automatically expires
Safety test It takes max. 30 min and finishes automatically or it is aborted,
if: boiler temperature is > 110°C or the „+“ button was not
pressed for 30 seconds
Operation range of automatic
setting of C.H. return
connection to determined
value
Between 60°C and 80°C
Operation without settings
controlled by technician
Regulator is adjusted after setting by producer
Data storaging Only by sufficient energy > 160V.