Instruction manual
38
Too high flue gas temperature (warning)
Cause:
Control light 3 red:
Flue gas temperature > 300°C
Flickers
Temperature of flue
gas is too high
Boiler temperature
(°C)
Correction:
Reset:
Emergency program:
Actions of regulator:
By heating-up and refuelling, close the door
immendiately
In operation: After burning-out, clean the
boiler
Automatically at flue gas temperature <299°C
No
Flue gas temperature > 350°C, flue gas fan
stop
Flue gas temperature < 299°C, flue gas fan
start
Overheating (warning)
Cause: Boiler is on and its temperature is > 90°C
Fuel surplus, circuiting pump error
Overheating
DO NOT OPEN!
Boiler temperature
(°C)
Control light 3 red:
Correction:
Reset:
Emergency program:
Actions of regulator:
Flickers
Load less fuel or remove error
Automatically at boiler temperature < 89°C
No
Boiler temperature > 90°C, flue gas fan stop
V1=0 %, V2=min. 25 % open
Boiler temperature < 89°C, flue gas fan start.
V1 and V2 are adjusted after setting.
Incorrectly measured values of flue gas temperature (error)
Cause: Measured values < -20°C or > 499°C
Control light 2 yellow
Correction:
Lights
Check sockets and inlet conductors!
Replace sensors, if necessary!
Error in measuring
of temperature
Fluegas temperature
(°C)
Reset:
Emergency program:
Actions of regulator:
Automatically after error removing.
Yes, burn-out possible
Regulator works with big amount of
alternative air V1 and V2. Boiler has to be
switched off manually and let to burn out by
the „-“ button. While warming, no line graph
is displayed.