Instruction manual

20
Settings for the commission of the ATTACK DPX LAMBDA .
The start-up of device is enabled, when the minimum requirements for test- or heating operation
are fulfilled (see chapter 1.2). Afterwards it is necessary to carry out the following settings.
Settings with usage of the service technician´ s code
The menu button
“enables entrance into menu “Selection”, where it is possible to select the
„Settings“ submenu by buttons “+” or “-”. The choice of “Settings” is confirmed with the button
”.
The exit from the submenu automatically occurs after setting of the "connection valve" with the
menu button “ ”; after exit it is automatically switched to the operating display.
If no button is pressed for 1 min., it is automatically switched to the operation display.
Settings:
Menu Submenu Indication
Information
Test of device
Safety test
Code insert
---
Set the code by „+“ button. Random
number lights on the left side. Insert code
and confirm by „“ button. Technician´s
number is available from supplier of the
boiler.
01 :Language
German DE
English GB
Italian IT
French FR
Swedish SE
Polish PL
Slovak SK
Czech CZ
Dutch NL
Danish DK
Hungarian HU
Slovenian SI
Function: Setting of national language
02 : Setting of boiler
°C 85
Function: Set boiler temperature
Producer: 85°C
Range of setting: 75°C – 85°C
03 : Setting of TAG
°C 180
Function: After setting of flue gas
temperature (nominal 180°C boiler output).
Producer: 180°C
Range of setting: 110°C up to 240°C
Tip: TAG = flue gas temperature
04 : Setting of O
2
% 6,0
Function: Setting of O
2
value for
combustion 6 %
Producer 6,0 %
Range of setting: 4,0 % up to 8,0 %
Setting
05 : Start TAD
K 60
Function: to reach sufficient output before
the feeding door is closed
Producer: 60K
Range of setting: 25K up to125K
Tip: TAD= temperature difference. It is