Specifications

GURANTEED TECHNICAL PARTICULARS - ANNEXURE-VII
Ports 2 Serial, 6 USB (4+2), 1 VGA
Keyboard USB Keyboard. Same make as that of Server.
Mouse USB Optical Mouse. Same make as that of Server.
Backup Device DAT 320 SAS Internal Tape Drive with Backup Software, Data
Cartridge & Cleaning Catridge
Optical Drive DVD ROM Drive
Power Supply 1+1 Redundant Power Supply or better
Bays 8 Hot Swap Hard Disk Bays
Housing Tower Type
Management Software OEM Server Management Software, System Health Monitoring,
Remote Management on Windows
Certifications Windows Server 2003/2008
Security Power on Password
1.8
Server for Talwara, Sundernagar & Nangal with the same Config as at 1.7 but with
CPU 1 x Intel Xeon Quad Core Processor E5620 (2.4 GHz or higher with
12MB Cache or higher & 5.86 GT/s or higher ) or Higher
Memory 12 GB Registered DDR3 with ECC, 1066 MHz or higher Memory
upgradable to 192 GB through 12 DDR3 DIMMs
Monitor 19" LCD Monitor, TCO'05 Certified, Make same as that of Server
2 SYSTEM SOFTWARE
2.1 WINDOWS 2008 ENTERPRISE SERVER 64 Bit Edition OLP WITH MEDIA ( Incl Client Access
License for 10 users)
2.2 EXCHANGE SERVER 2010 ENTERPRISE OLP WITH MEDIA AND FOREFRONT THREAT
MANAGEMENT GATEWAY 2010 with MEDIA Version
2.3 EXCHANGE SERVER 2010 STANDARD OLP WITH MEDIA or Latest Version
3
POWER CONDITIONING EQUIPMENT
3.1
ON LINE UPS OF 5 KVA RATING
Power Rating
5KVA
Technology DOUBLE CONVERSION On-line UPS using IGBT & having Isolation
Transformer for total isolation from mains.
INPUT
Nominal Voltage Range
230 V - 25 % + 10% , Single Phase
Nominal frequency Range
50 Hz ± 5%
Power Factor
Not less than 0.95
Wave Form
Sinusoidal
OUTPUT
Continuous output Power
5 KVA/ 3.5 KW or higher
Voltage
230 V, Single Phase
Voltage Regulation
Not more than 2%
Frequency
50 Hz ± 0.5 Hz
Overload Capacity
110% for 10 minutes and 150% for 10 seconds120% for 30 secs
Wave Form
Sinusoidal
Load Power Factor
0.7 to 0.8
COMPUTER & COMMUNICATION INTERFACE
Should be available & the software should be capable of monitoring UPS activity & to ensure orderly
shutdown of the server in case of battery low voltage/discharged condition. Software required for
Windows Server 2008. SNMP Based real time monitoring of all vital parameters such as Input
voltage, Output Voltage, Output Load, Battery Voltage om Windows.
MEASURING INSTRUMENTS (ANALOG OR DIGITAL)
Input Voltage , Output Voltage & Frequency, Batt Voltage, Batt Current, Load
Current in Amps
Minimum 100 records of faults generated with date and time. FIFO method
PROTECTION
Over Load protection
MCBs both at Input & Output, Over Voltage protection
ADDITIONAL FEATURES
Static and Manual bye pass switch should be available
Caster wheels should be available for easy mobility of the UPS Unit of 5 KVA.
Cold start facility on full load should be available.
Noise level less than 45 db
INDICATIONS
Battery charging/status Indication
Bye-pass ON/OFF indication
Mains ON/OFF indication
Inverter ON/OFF
ALARM WITH INDICATIONS
6