User`s manual
User manual Version 1.1
ABLELink
®
Ethernet Serial Server SE5002
Copyright © 2006 Atop Technologies, Inc.
All rights reserved. Designed in Taiwan.
- 21 -
Click on “COM1” link and the following screen shall appear.
Configure SE5002 as TCP server
Input local listening port “4660”
1.To enable IP filter:
Check “IP filter”
Input source IP on “Source IP”
2.If not to enable IP filter:
Don’t check “IP filter”
Input idle time on “Please input idle time to send TCP keep-alive packet(sec)
:
”( 2->the sending
TCP keep-alive packet period will be 2*10 sec)
Input TCP Inactivity time in “TCP Inactivity Time Before Disconnect( sec)
:
”( 2->TCP Inactivity
beyond 2 sec will cause disconnect )
Click on “Save Configuration” button to save the changes
Notes:
1. One may configure COM1 or COM2 parameter by choosing COM1 or COM2 Link
2. IP filtering function is disabled by setting FILTER_IP to “0.0.0.0”.
3. IP filter is disabled by default
4. If IP filter is enabled, only source IP assigned is connected to SE5002.