User`s manual
Quick Start Guide Version 1.2
GW51C-MAXI Serial Server
3
may use Monitor.exe to activate this function. Please refer to the dialog window below.
4.2.5. Configure by console mode
1. Set MODE switch SW1 to ‘OFF’ and SW2 to ‘ON’, then Power off GW51C-MAXI Serial Server
2. Use a PC to connect to GW51C-MAXI Serial Server’s console with RS-232 cross over cable
3. Power on Serial Server, then Open terminal program from your computer and Set to 9600, 8, n, 1
without flow control for console port communication.
4. The following configuration operations are totally the same as those configure by telnet.
5. After finishing console settings, power off GW51C-MAXI Serial Server, put SW1 and SW2 back to
previous setting.
5. Pin Assignments
5.1. 8 pin Mini DIN connector
-Atop provides Mini DIN connector to DB9 connector cable, the pin
assignments is shown in the following table and RS-485 2 or 4 pins assignments of DB9 connector
are different from those of Mini DIN connector.
Pin#
RS-232
Full Duplex
RS-485
2 wire, Half Duplex
RS-422/RS-485 4 wire,
Full Duplex
1 DCD N/A N/A
2 RXD N/A (reserved)
TXD+
3 TXD
DATA+
RXD+
4 DTR N/A N/A
5 SG (Signal Ground) SG (Signal Ground) SG (Signal Ground)
6 DSR N/A N/A
7 RTS
DATA- RXD-
8 CTS N/A (reserved)
TXD-
9 N/A N/A N/A