Product specifications

7.2. Minimum clearances.
For servicing and maintenance purposes, a
minimum clearance of 600mm to the front, 150mm
above, 750mm below (allowing for installation of
the expansion vessels), or 250mm below for use
with side mounted Pre-Assembled kit, and 100mm
to either side of the boiler case is required. (fig. 10
& fig 11)
Figure 10: Dimensions & minimum clearances
Figure 11: Dimensions & minimum clearances
Note
The T & P valve discharge pipe is not shown
(on LHS).
Warning : When removing the red caps from
the boiler pipes, dead water will come out,
which can cause stains. Take care!
7.3 Boiler location.
The Atmos Multi is not suitable for external
installation.
While the appliance itself is provided with integral
frost protection, it must be installed in a room that
stays free of frost. This is to prevent pipes or the
safety valves from freezing. If the selected room
does not meet this requirement, measures must be
taken to prevent freezing.