8. FAULTS
When the controller detects a fault, the red fault LED flashes (above the
Reset button) and a fault code is shown on the Temperature display.
After the fault has been remedied, the controller can be restarted by
pressing the Reset button for 5 seconds.
The following faults are detected and displayed:-
Temperature
display
Description
Possible cause/remedy
10, 11, 12, 13, 14
Sensor fault S1
Check the wires for breaks
Replace S1
20, 21, 22, 23, 24
Sensor fault S2
Check the wires for breaks
Replace S2
0
Sensor fault after self
-
check
Replace boiler sensor S1 and/or S2
1
Temperature too high
Air in system
Pump does not run
Too little circulation in system, radiators closed,
pump setting too low
2
Exchange S1 and S2
Check the cable loom
Replace S1 or S2
4
No flame signal after 4 ignition
attempts
Gas tap closed
Incorrect ignition distance
Gas inlet pressure too low or disappears
Gas valve or ignition unit does not receive voltage
Further info can be found on Technical Data Sheet
TDS012 available on www.atmos.co.uk
5
No flame signal after 4 restart
attempts
Condensate discharge blocked
Check setting of gas valve
Further info can be found on Technical Data Sheet
TDS013 available on www.atmos.co.uk
6
Flame detection fault
Replace ignition cable + spark probe
Replace ignition unit
Replace controller
8
Fan speed incorrect
Fan rubs against casing
Wiring between fan and casing
Check the wires for poor contact (tacho signal)
Replace fan
29, 30
Gas valve relay fault
Replace
controller
8.1 Display last fault code.
It is possible to display the last fault code as follows:
Set the appliance in the off mode using the On/Off key (
-
on the service display).
Press the Service key, until the last fault code appears flashing on the temperature display.
When no fault has occurred no code will be displayed.
By pressing simultaneously the Service key and the “-“ key the fault code will be erased.