Owner`s manual
AtlasSound.com – 14 –
Specifications are subject to change without notice.
Owner’s Manual
ECM-15SH
AC
Power Conditioner & Suppression Module
1601 Jack McKay Blvd. • Ennis, Texas 75119 U.S.A.
Telephone: 800.876.3333 • Fax: 800.765.3435
ECM-15SH SPECIFICATIONS
General
Type Power Conditioner Suppressor Module
Power Requirements 120V 60Hz
Power Consumption .5W
RoHS Compliant Yes
Panel
Switched Outlets Two, 15A
Spike & Surge Suppression H-N, N-G, H-G
Manual Override Slide switch
Extreme Voltage Shutdown (EVS) Below 102V or Above 132V AC Line (When Used With
ECS-6RM)
Connectors 5 Position Phoenix Euro Block Style
Fuse Protection 15A Slow Blow
DCV Remote Trigger 5–24DCV
Remote Trigger SPST Contact
Status Signals Output for Voltage and Current Data (All data signals are
low voltage and current)
Indicators Incoming AC, Active, AC Fault
Power Cord 9ft (3m), 14 gauge
Technical Data
Current Rating 15 amps
Operating Voltage 102 to 132 VAC
High Voltage Surge Protection Trigger at 133 VAC, 1ms typically (When Used With ECS-
6RM)
Spike & Surge Suppression H-N, N-G, H-G
Low Voltage Protection Trigger 101 VAC, 1ms typically (When Used With ECS-6RM)
Spike Protection Modes Circuitry on incoming AC Mains.
Minimum Spike Clamping Voltage 460VRMS@3,000amps
Maximum Spike Clamping Voltage 6000v
Maximum Spike Clamping Response Time 1 nanosecond
Spike Clamping Voltage @ 100A 1250Vp for 20µs
Maximum surge current 6,500 amps
Energy Rating @ 2ms 600 Joules
Noise Attenuation EMI/RFI Sequencer 10dB@10kHz,40dB@100kHz,100dB@10MHz
Temperature Range 5º to 35º C
Humidity Range 5% to 95% R.H.
Mechanical
Chassis Finish Black
Mounting Side bracket adjustable
Dimensions 1.75" H x 8.5" W x 5.0" D (4.5 cm x 21.6 cm x 12.7 cm)
Weight 4.5 lbs (2.04 kg)
Agency Listings MET (UL 1449 Code)