Owner`s manual
– 13 – AtlasSound.com
Specifications are subject to change without notice.
Owner’s Manual
ECM-15SH
AC
Power Conditioner & Suppression Module
1601 Jack McKay Blvd. • Ennis, Texas 75119 U.S.A.
Telephone: 800.876.3333 • Fax: 800.765.3435
Issue 5: ECS-6RM Channel Activation Status LED is flashing and AC power at the ECM module is active.
Possible Cause: The AC Mains Voltage at the ECM Module reached between 127- 132VAC or the voltage dropped between 107 -
101VAC.
Action Needed: The ECS-6RM must be re-sequenced to turn off the LED, measure the AC mains before restarting the ECM
Module. If the voltage is between 117VAC and 123VAC you may proceed to reset the ECS-6RM by restarting the
startupsequence.NOTE:ItisimportanttohaveallequipmentthatwasconnectedtothatACMainsLineinspect-
ed for proper operation. If the problem persists, contact your local power company for the cause of unstable AC
line conditions.
Issue 6: No Voltage Reading at the ECS-6RM.
Possible Cause #1: Check Issues 1 - 4 first.
Possible Cause #2: Proper Channel is not selected for viewing.
Possible Cause #3: Channel Activation LED is Illuminated Green but the Voltage display is not on. Check the wiring between the
ECS-6RM Channel and the ECM module. “V”, “A” and “D” must be in the correct polarity.
Issue 6: No Current Reading at the ECS-6RM, meter reads ‘nA’.
Possible Cause #1: An ECM-15 Module is connected. This module does not support current read out.
Possible Cause #2: Check Issues 1 - 4 first.
Possible Cause #3: Current Draw of ECM Module must exceed 500mA to register.
Possible Cause #4: Proper Channel is not selected for viewing.
Possible Cause #5: Channel Activation LED is Illuminated Green but the Current display reads “nA”. Check the wiring between the
ECS-6RM Channel and the ECM module. “V”, “A” and “D” must be in the correct polarity.