Spec Sheet
DOC:3248
REV.:V1.0
DATE:2022-04-16
SHEET: 7 / 10
4. BMS/PCM Parameters:
NO
Indicator item
Windows
default
Optional
Remarks
1
Cell overcharge
protection
Cell overcharge alarm voltage
3600mV
Optional
Cell overcharge protection voltage
3650mV
Optional
Cell overcharge protection delay
4S
Optional
Removal of Cell
over
voltage protection
Cell overcharge protection Relief
voltage
3380mV
Optional
Capacity Relieve
SOC<
96%
Optional
Discharge release
Discharge current> 1A
2
Cell over discharge
protection
Cell over discharge alarm voltage
2900mV
Optional
Over discharge
protection for 30
seconds
After that, it is still
unable to recover
When it comes back,
it will enter Low
power mode
Cell over discharge protection
voltage
2800mV
Optional
Over discharge protection
delayarge protection delay
1S
Optional
Release of Cell over
discharge
protection
Cell over discharge protection
Relief voltage
3000mV
Optional
Discharge of charge
The access charger may be
activated.
3
Overall overcharge
protection
Overall overcharge alarm voltage
54V
Optional
Overall overcharge protection
voltage
54.75V
Optional
Overall over-charge protection
delay
4S
Optional
Overall over voltage
protection lifted
Overall over-charge protection release
voltage
50.6V
Optional
Capacity Relieve
SOC<
96%
Optional
Discharge release
Discharge current> 1A
4
Overall over
discharge
protection
Protection
Overall over amplifier alarm voltage
43.5V
Optional
Overall over
discharge protection voltage
42V
Optional
Overall overplay protection delay
1S
Optional
Over discharge
protection is lifted.
Overall
over discharge protection Relief
voltage
45V
Optional