Instruction manual
22 2954 2100 01
QAS 14 - 20 Pd
Control setup: overview parameters
Power setup: overview parameters
USW
Alarm Type
High
(Low / High)
1475
Enable
OFF
1476
Fail Class
Warning
1473
Output Relay A
R0
1474
Output Relay B
R0
1470 Coolant Temperature 2
SERVICE LEVEL
5.0s
(0 ... 150.0)
(0.0 ... 600.0)
1454
Enable
ON
1455
Fail Class
Shutdown
1452
Output Relay A
R0
1453
Output Relay B
R0
1450 Emergency Stop
MASTER LEVEL
1451
Delay
0.0s
1444
Enable
ON
1445
Fail Class
Shutdown
1441
Delay
1.0s
1442
Output Relay A
R0
(R0 ... R3)
(OFF / RUN / ON)
(Warning / Trip / Trip+Stop / Shutdown)
(0.0 ... 60.0)
1443
Output Relay B
R0
1431
Overspeed S2
1650rpm
1440 Engine Failure
SERVICE LEVEL
1426
Fail Class
Shutdown
1430 Overspeed
MASTER LEVEL
Output Relay B
R0
1425
Enable
ON
1421
Setpoint
1650rpm
1422
Delay
3.0s
1420 Overspeed
MASTER LEVEL
(R0 ... R3)
(OFF / RUN / ON)
(Warning / Trip / Trip+Stop / Shutdown)
(1 ... 2250)
1413
Output Relay A
R0
1414
Output Relay B
R0
1402
Setpoint 3
Pump Relay
1410 Fuel High
1403
1412
Delay
5.0s
CUSTOMER LEVEL
1411
Setpoint 4
98.0%
Fill Check Delay
1404
Enable
60.0s
1400 Fuel Pump Logic
CUSTOMER LEVEL
1471
Setpoint
N/A
1472
Delay
USW
Alarm Type
High
(Low / High)
1466
Fail Class
Warning
(Warning / Trip / Trip+Stop / Shutdown)
1465
Enable
OFF
(OFF / RUN / ON)
1464
Output Relay B
R0
(R0 ... R3)
1460 Coolant Temperature 1
SERVICE LEVEL
1461
Setpoint
N/A
(0 ... 150.0)
USW
Sensor Type
N/A
(0 / 1 / 2)
1396
Fail Class
Warning
(Warning / Trip / Trip+Stop / Shutdown)
1395
Enable
OFF
(OFF / RUN / ON)
1394
Output Relay B
R0
(R0 ... R3)
1393
Output Relay A
R0
(R0 ... R3)
1392
Delay
20.0s
(0.0 ... 100.0)
1390 Fuel Level 1
CUSTOMER LEVEL
1391
Setpoint 1
5.0%
(0 ... 100)
1463
Output Relay A
(0.2 ... 100.0)
(R0 ... R3)
R0
(R0 ... R3)
1423
Output Relay A
R0
1424
1401
Setpoint 2
(R0 ... R3)
1462
Delay
5.0s
(0.0 ... 600.0)
20.0%
OFF
1405
(OFF / RUN / ON)
(0.1 ... 300.0)
(0 ... 100)
80.0%
R3
(R0 ... R3)
(1 ... 2250)
(0 ... 100)
(0 ... 100)
(R3)
(0.1 ... 300.0)
(R0 ... R3)
(R0 ... R3)
(OFF / RUN / ON)
(Warning / Trip / Trip+Stop / Shutdown)
(0.0 ... 180.0)
(R0 ... R3)
(R0 ... R3)
(R0 ... R3)
(OFF / RUN / ON)
(Warning / Trip / Trip+Stop / Shutdown)
1386
Fail Class
Warning
(Warning / Trip / Trip+Stop / Shutdown)
1385
Enable
OFF
(OFF / RUN / ON)
1384
Output Relay B
R0
(R0 ... R3)
1383
Output Relay A
R0
(R0 ... R3)
1382
Delay
5.0s
(0.0 ... 100.0)
1380 VDO 2.2
SERVICE LEVEL
1381
Setpoint
N/A
(40 ... 150)
1485
Enable
OFF
1486
Fail Class
Warning
1483
Output Relay A
R0
1484
Output Relay B
R0
1481
Setpoint
N/A
1482
Delay
5.0s
1480 Oil Pressure
SERVICE LEVEL
USW
Alarm Type
Low
(0.0 ... 600.0)
(Low / High)
(0.0 ... 15.0)
(R0 ... R3)
(R0 ... R3)
(Warning / Trip / Trip
+
(OFF / RUN / O
N)
1736
Type
High
(Low / High)
1735
Fail Class
Warning
(Warning / Trip / Trip
+
1733
Output Relay B
R0
1734
Enable
OFF
1731
Delay
10.0s
1732
Output Relay A
R0
1730 Dig.Input 4 / GCB closed
CUSTOMER LEVEL
High
1720 Low Fuel Switch
CUSTOMER LEVEL
(Low / High)
1715
Fail Class
Shutdown
1716
Type
Low
1713
Output Relay B
R0
1714
Enable
ON
1712
Output Relay A
R0
1711
Delay
3.0s
Type
Coolant Temp. & Cool. Level
R0
R0
RUN
1702
Output Relay A
1703
Output Relay B
1721
Delay
3.0s
(R0 ... R3)
(OFF / RUN / O
N)
(Warning / Trip / Trip
+
(Low / High)
1704
Enable
1705
1722
Output Relay A
R0
1723
Output Relay B
R0
1860 Run Status
SERVICE LEVEL
1861
Delay
5.0s
1862
Output Relay A
R0
1863
Output Relay B
R0
1870 W/L Input
SERVICE LEVEL
1871
Delay
3.0s
1872
Output Relay A
R0
1873
Enable
RUN
1874
Type
Low
1880 Static Charger
SERVICE LEVEL
(Low / High)
1881
Delay
10.0s
1882
Output Relay A
R0
1883
Enable
ON
1884
Type
High
(R0 ... R3)
(R0 ... R3)
(0.0 ... 100.0)
1710
SERVICE LEVEL
3.0s
1491
Setpoint
1700
1701
Delay
1490 Fuel Level 2
Shutdown
Low
Fail Class
1706
1492
Delay
1494
Output Relay B
(R0 ... R3)
(R0 ... R3)
Enable
(OFF / RUN / O
N)
Output Relay A
R0
R0
Low Oil Pressure
1493
1495
Fail Class
OFF
1496
(R0 ... R3)
(R0 ... R3)
(Warning / Trip / Trip
+
(OFF / RUN / O
N)
ON
(0.0 ... 100.0)
CUSTOMER LEVEL
N/A
(R0 ... R3)
(0.0 ... 100.0)
(0 ... 100)
(0.0 ... 100.0)
SERVICE LEVEL
20.0s
(OFF / RUN / O
N)
(Warning / Trip / Trip
+
(Low / High)
1726
Type
1724
Fail Class
Trip + Stop
1725
(OFF / RUN / O
N)
(OFF / ON)
(Low / High)
(0.0 ... 100.0)
(R0 ... R3)
(R0 ... R3)
(0.0 ... 100.0)
(R0 ... R3)
(OFF / RUN / O
N)
(0.0 ... 60.0)
(R0 ... R3)
Warning
(Warning / Trip / Trip
+
Enable
1864
Enable
OFF
(OFF / ON)
(0.0 ... 100.0)
(R0 ... R3)
(R0 ... R3)
2050
SERVICE LEVEL
2051
Df max.
4.0Hz
(0.0 ... 5.0)
f/U Limits
5%
(2 ... 10)
2052
DU max.
50%
(1 ... 100)
(30.0 ... 990.0)
3072
Delay
300.0s
3073
Test Breaker
OFF
(ON / OFF)
3071
Setpoint
3070 Test
CUSTOMER LEVEL