Product Manual
Table Of Contents
- Table of contents
- 1 Safety precautions
- 2 General description
- 3 Elektronikon Base Controller
- 3.1 ElektronikonTM Base Controller
- 3.2 Control panel
- 3.3 Icons used on the display
- 3.4 Main screen
- 3.5 Main function
- 3.6 Shutdown warning
- 3.7 Shutdown
- 3.8 Service warning
- 3.9 Scrolling through all screens
- 3.10 Calling up running hours
- 3.11 Calling up motor starts
- 3.12 Calling up module hours
- 3.13 Calling up loading hours
- 3.14 Calling up load solenoid valve
- 3.15 Calling up/resetting the service timer
- 3.16 Calling up/modifying pressure band selection
- 3.17 Calling up/modifying pressure band settings
- 3.18 Calling up/modifying the unit of temperature
- 3.19 Calling up/modifying the unit of pressure
- 3.20 Calling up/modifying backlight time
- 3.21 Activating automatic restart after voltage failure
- 3.22 Keyboard lock
- 4 Installation
- 5 Operating instructions
- 6 Maintenance
- 7 Adjustments and servicing procedures
- 8 Problem solving
- 9 Technical data
- 10 Instructions for use
- 11 Guidelines for inspection
- 12 Pressure equipment directives
- 13 Declaration of conformity
3.7 Shutdown
Description
The compressor will shutdown:
•
In case the temperature at the outlet of the compressor element exceeds the shutdown level (detected
by temperature sensor (TT11) or by temperature switch (TSHH11)).
• In case of error of the outlet pressure sensor (PT20) or temperature sensor (TT11).
• In case of overload of the compressor motor (M1)
Compressor element outlet temperature
If the outlet temperature of the compressor element exceeds the shutdown level (factory setting 115˚C/
239˚F):
• The compressor will shutdown.
• Alarm LED (5) will flash.
• The following screen will appear:
Main screen with shutdown indication, element outlet temperature
• The related pictograph
will appear flashing.
•
Scroll Up or Down buttons (4-8) until the current element outlet temperature appears.
Shutdown screen, element outlet temperature
The screen shows that the temperature at the outlet of the compressor element is 117 ˚C.
Instruction book