Troubleshooting .
Alarm codes on the control panel:
The buzzer can be stopped or reset by pressing one of the following keys:
, or
Code
Condition under
which the error
occurs
Cause
Consequences Repair
Err
03
Water temperature
sensor in the pocket
faulty
Sensor cut out or
shorted
No heating
High-pressure safety device
activated (Err 25)
Check the connections or replace the
sensor wiring
Err
06
Anti-corrosion connection
shorted
Wiring or anti-
corrosion anode
shorted
Anti-corrosion protection
deactivated, risk of corrosion.
Check the wiring connections
Replace the wiring and/or the anti-
corrosion wiring
Err
07
Anti-corrosion connection
broken
No water in the tank or
anti-corrosion wiring
cut
No heating
Put water in the tank
Replace the wiring and/or the anti-
corrosion wiring
Err
09
Water temperature too
high
(> 80°C)
Electric resistor
charged permanently
3 HS sensor
Risk of triggering the mechanical
safety device
No heating
Check the connections and the position of
sensor 3
Check that the electric backup is not
permanently working
Reset the mechanical safety device if
necessary and contact your reseller
Err
21
Measured temperature
outside the limits
Temperature sensor
(air inlet) cut out or
shorted
Operating ranges not respected
AUTO mode: heating with the
electric backup
ECO mode: no heating
Check the connections or replace the
sensor wiring
Err
22
Evaporator temperature
sensor faulty
Sensor cut out or
shorted
Hot gas valve fault
Fan fault
Defrost function compromised
Risk of damage to the compressor
AUTO mode: heating with the
electric backup
ECO mode: no heating
Check the connections or replace the
sensor wiring
Check that the fan and the hot gas valve
are in good working order
Err
24
Measured temperature
outside the limits
Air temperature
outside the operating
range.
Heat pump working outside the
range
AUTO mode: heating with the
electric backup
ECO mode: no heating
Install the water heater according to the
recommendations in the manual
Check the FAN setting (see page 15)
Check the connections and the position of
sensor 1
Err
25
Pressure switch alarm
(high pressure fault)
High pressure value
too high
Compressor power supply failure
AUTO mode: heating with the
electric backup
ECO mode: no heating
Check that the air temperature has not
exceeded 35°C
Press the mode key to clear this fault.
Contact your reseller.
Err
28
Defrost malfunction
Shortage of fluid
Hot gas valve fault
Defrost function does not work and
the evaporator is obstructed
AUTO mode: heating with the
electric backup
ECO mode: no heating
Check the activation of the hot gas valve
in installer mode
Check that the fan is in good working
order
Press the mode key to clear this fault.
Contact your reseller.
Err
30
Heat pump works for
more than 50h without
stopping
Heat pump fault
Shortage of fluid
Compressor fault
Heating time is too long
Risk of shortage of hot water
AUTO mode: heating with the
electric backup
ECO mode: no heating
Contact your reseller