Specifications
NEW!
1419
TRANSDUCERS
TRANSDUCERS
23
WE MAKE IT EASY.
kele.com 888-397-5353 USA
March 2014
• DIN rail mounting
• Pressure gauge
• PWM input
• Tri-state input
• Feedback and span
adjustment
• Failsafe
• Manual output adjustment
Supply Voltage
Without Options None, loop powered
With Options 24 VAC/VDC
Supply VA
With F, M, V Options 180 mA maximum (half-wave)
With UCO Options 100 mA maximum (half-wave) at 24
VAC, 50 mA at 24 VDC
Input 4-20 mA, 2-10 VDC (V option)
Input Impedance 500Ω @ 4-20 mA, 160 kΩ (V option)
Wiring Terminations Screw terminals
Air Capacity 515 scim (135 cm
3
/s) @ 20 psig
(138 kPa) supply
Air Connections Brass barbs for 1/4" OD tubing
Air Consumption 0.008 scfm (3.8 cm
3
/s) @ 20 psig
(138 kPa) supply
Maximum Pressure 25 psig (172 kPa)
Linearity 2% of span
Hysteresis 1% of span
Output 3-15 psig (21-103 kPa)
Operating Temperature 32° to 122°F (0° to 50°C)
Operating Humidity 5 to 95% RH (non-condensing)
Weight 1.4 lb (0.64 kg)
Warranty 1 year
ELECTRONIC / PNEUMATIC TRANSDUCER
UCP-422 SERIES
DESCRIPTION
The UCP-422 Series electronic/pneumatic transducer
provides low-cost pneumatic control of valves, dampers, or
other pneumatic devices. The UCP-422 consists of a totally-
enclosed transducer with provisions for optional DIN rail or
surface mounting in either of two planes. Externally-mounted
pneumatic filters are not required. Quick-disconnect terminals
provide easy wiring removal for servicing. When DIN rail
mounting is used, this compact device requires only a 4"H x
2"W (10.2 x 5.1 cm) mounting area, providing efficient use of
panel space.
FEATURES
• Slim-line mounting to save panel space
• Universal mounting tabs
• Totally enclosed
• 1/4" (0.64 cm) barbed tube connectors
• Quick-disconnect terminals
• Loop-powered control (base model)
• No external filter required
• Excellent linearity
• Low hysteresis
• No calibration required
OPERATION
The UCP-422 Series accepts a 4-20 mA signal and outputs
3-15 psig (20.7-103.4 kPa). Used in its base configuration, it
requires no power supply for controlling pneumatic devices.
Upon a loss of signal or power, the UCP-422 will eventually
bleed the pressure in the branch line. This transducer is well
suited for the control of small to medium volume loads, such
as small to medium pneumatic actuators. Large volume loads,
such as large pneumatic actuators or long tubing runs may
also be controlled but will exhibit slower response time.
4.8
(12.2)
4.0
(10.1)
6.3
(16)
3.4
(8.6)
0.7
(1.8)
4.6
(11.7)
2.0
(5.0)
2.75
(6.9)
Optional
DIN Rail
Adapter
COM
SIG IN +
Removable
Mounting Tabs
Removable
Mounting Tabs
in
(cm)
Optional Gauge Assembly
( rotate 90 degrees
for two-position display)
Branch
Main
B
M
UCP-422
4-20 mA
Signal
–
+
SPECIFICATIONS
DIMENSIONS
OPTIONS
Shown with Optional Pressure Gauge