Specifications

NEW!
TRANSDUCERS
1452
NEW!
TRANSDUCERS
23
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
kele.com888-397-5353 USA
March 2014
INSTALLATION
Mount the device inside an enclosure near the controlled equipment, avoiding areas of temperature extremes, corrosive vapors,
or electromagnetic interference. Use track slots for screw attachment. Note: Protect circuit board from metal filings created during
panel construction. Make all connections according to wiring diagram or as shown in the job diagram and in compliance with
national and local codes. Use shielded #18 gauge cable for connections from the transducer to the controller. The unit comes
precalibrated for easy application.
CHECKOUT
Tools required: Volt ohmmeter, signal analyzer or other signal source.
1. Verify that the input selector switches are in the correct position for the input signal to be used.
2. Verify that either 24 VAC or VDC is present at the power terminals.
3. With the controlled device disconnected, connect an ohmmeter to the B and R terminals on the RES-1E output. With no signal
input, the resistance between B and R should be at minimum, and the resistance between W and R should be at maximum
resistance.
4. Apply the minimum input signal for the range selected to the input terminals. The RES-1E should output less than 2% of full
range, the minimum resistance of the RES-1E.
5. Slowly increase the input signal. The resistance reading will increase linearly toward full range. If the resistance does not vary
with the input signal, check the polarity of the input wiring.
LED INDICATION
Steady green: power on and idle
Slow green blink (three blinks/pause): Signal loss hold
Rapid green blink: PWM pulse being received
CAUTION: Make all connections with power removed. Failure to do so could result in circuit board damage.
UNIVERSAL RESISTANCE TRANSDUCER
RES-1E SERIES
INSTALLATION AND CHECKOUT
ORDERING INFORMATION
MODEL DESCRIPTION
RES-1E Universal resistance transducer, 0-135 output
RES-1E-1000 Universal resistance transducer, 0-1000 output
RES-1E-270 Universal resistance transducer, 0-270 output
RES-1E-500 Universal resistance transducer, 0-500 output
RES-1E-S Universal resistance transducer, special range output
(specify range; min span = 30 , maximum span = 1 M, start can be above zero)
RELATED PRODUCTS
R-PAK Resistance board only for RES-1E (specify range, minimum span 3, maximum span 1 M)