Specifications

NEW!
1451
TRANSDUCERS
TRANSDUCERS
23
WE MAKE IT EASY.
kele.com 888-397-5353 USA
March 2014
Separate 24V Supplies for Power and Signal
** PWM signal input terminals are optoisolated and polarity insensitive.
PWM computer contacts can switch either PWM wire lead.
BAS Controller
PWM Contacts**
24 VAC/VDC
Power
Res Output
BRW
Fallback
BRW
Pulse
Signal
24V
COM
COM
I-V
Sig
12345678
STAT
24 VAC/VDC
Power
+
Resistance Output
to controlled device
Optional Connection
to back up thermostat
or potentiometer
Optional Connection
to back up thermostat
or potentiometer
B-R Resistance increases
with signal increase
W-R Resistance decreases
with signal increase
B-R Resistance increases
with signal increase
W-R Resistance decreases
with signal increase
24 VAC/VDC
Power for PVM
Signal
BAS Controller
PWM Contacts**
Common 24V Supply for Power and Signal
Res Output
BRW
Fallback
BRW
Pulse
Signal
24V
COM
COM
I-V
Sig
12345678
STAT
Resistance Output
to controlled device
INPUT TYPE SIGNAL RANGE OPTIONS SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8
PWM 0.1-2.65 sec No PLMEM 0 0 0 0 0 0 0 0
PWM 0.1-2.65 sec With PLMEM 0 0 0 1 0 0 0 0
PWM 0.1-5.2 sec No PLMEM 0 0 0 0 1 0 0 0
PWM 0.1-5.2 sec With PLMEM 0 0 0 1 1 0 0 0
PWM 0.1-12.85 sec No PLMEM 0 0 0 0 0 1 0 0
PWM 0.1-12.85 sec With PLMEM 0 0 0 1 0 1 0 0
PWM 0.1-25.6 sec No PLMEM 0 0 0 0 1 1 0 0
PWM 0.1-25.6 sec With PLMEM 0 0 0 1 1 1 0 0
PWM 0.59-2.93 sec No PLMEM 0 0 0 0 0 0 1 0
PWM 0.59-2.93 sec With PLMEM 0 0 0 1 0 0 1 0
POWER LOSS MEMORY, PWM INPUT:
At powerup, the resistance output will go to the value set by the last PWM pulse before power was lost. The output will remain at
this value until a new PWM pulse is received.
If power loss memory is disabled, the resistance output will go to minimum at powerup and remain there until a new PWM pulse is
received.
Option “PLMEM” = power loss memory
UNIVERSAL RESISTANCE TRANSDUCER
RES-1E SERIES
PWM CONTROL
PWM CONTROL WIRING