Specifications

NEW!
TRANSDUCERS
1450
NEW!
TRANSDUCERS
23
WHEN YOU NEED IT RIGHT, RIGHT NOW, CALL KELE.
kele.com888-397-5353 USA
March 2014
* For analog inputs that are valid all the way to zero, there is no condition where power loss memory and signal loss hold apply.
INPUT TYPE SIGNAL RANGE OPTIONS SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8
Analog 0-5V * 1 1 0 0 0 1 1 0
Analog 0-10V * 0 1 0 1 0 1 1 0
Analog 0-15V * 0 0 0 0 1 1 1 0
Analog 0-20 mA * 1 1 1 1 1 1 1 0
Analog 1-5V No PLMEM, no SLH 1 1 0 0 0 0 0 1
Analog 2-10V No PLMEM, no SLH 0 1 0 1 0 0 0 1
Analog 3-15V No PLMEM, no SLH 0 0 0 0 1 0 0 1
Analog 4-20 mA No PLMEM, no SLH 1 1 1 1 1 0 0 1
Analog 1-5V No PLMEM, with SLH 1 1 0 0 0 0 1 1
Analog 2-10V No PLMEM, with SLH 0 1 0 1 0 0 1 1
Analog 3-15V No PLMEM, with SLH 0 0 0 0 1 0 1 1
Analog 4-20 mA No PLMEM, with SLH 1 1 1 1 1 0 1 1
Analog 1-5V With PLMEM, with SLH 1 1 0 0 0 1 1 1
Analog 2-10V With PLMEM, with SLH 0 1 0 1 0 1 1 1
Analog 3-15V With PLMEM, with SLH 0 0 0 0 1 1 1 1
Analog 4-20 mA With PLMEM, with SLH 1 1 1 1 1 1 1 1
POWER LOSS MEMORY, ANALOG INPUT WITH NON-ZERO START VALUE:
At powerup, if analog input is below normal start value, the resistance output will go to the value set by the last valid analog input
before power was lost.
If power loss memory is disabled and, at powerup, analog input is below normal start value, the resistance output will go to minimum
until a valid analog input is received.
SIGNAL LOSS HOLD, ANALOG INPUT WITH NON-ZERO START VALUE:
If the analog input drops below the normal start value, the resistance output will stay at the value set by the last valid analog input.
If signal loss hold is disabled and the analog input drops below the normal start value, the resistance output will go to minimum until
a valid analog input is received.
Option “PLMEM” = power loss memory, option “SLH” = signal loss hold
Res Output
BRW
Fallback
BRW
Pulse
Signal
24V
COM
COM
I-V
Sig
12345678
STAT
Analog Current or
Voltage Input Signal
+
+
Resistance Output
to controlled device
Optional Connection
to back up thermostat
or potentiometer
B-R Resistance increases
with signal increase
W-R Resistance decreases
with signal increase
24 VAC/VDC Power
Notes:
1. If the RES-1E input signal is voltage, multiple RES-1Es may be powered
from the same power supply or transformer.
2. If the RES-1E input signal is current from a current sourcing controller,
multiple units may be powered from the same power supply or transformer.
3. If input signal is current from a current sinking controller, each RES-1E must
have a separate power supply or transformer.
UNIVERSAL RESISTANCE TRANSDUCER
RES-1E SERIES
ANALOG CONTROL WIRING
CURRENT OR VOLTAGE ANALOG CONTROL