Specifications

NEW!
1449
TRANSDUCERS
TRANSDUCERS
23
WE MAKE IT EASY.
kele.com 888-397-5353 USA
March 2014
Supply Voltage 24 VAC ±10%, half-wave; or 24 VDC
±10%
Supply Current 220 mA @ 24 VAC, 100 mA @
24 VDC
Input Various selectable analog and pulse
width modulated (PWM)
Input Signal 0-20 mA, 4-20 mA, 0-5 VDC, 1-5
VDC, 0-10 VDC, 2-10 VDC, 0-15
VDC, 3-15 VDC, or PWM
Pulse Rate PWM time base selections
0.1-2.65, 5.2, 12.85, 25.6,
or 0.59-2.93 seconds
Input Impedance 250 (current); 27.5 k (voltage)
Wiring Terminations Screw terminals
Accuracy ±1% of span
Linearity ±1% of span
Output 0-135, 0-1000, 0-270, 0-500,
Special range (specify upon ordering,
min span = 30 ,
maximum span = 1 M)
Output Resolution 255 steps
Operating Temperature 32° to 158°F (0° to 70°C)
Operating Humidity 5% to 95% RH (non-condensing)
Dimensions 3.3"H x 6.5"W x 1.3"D
(8.3 x 16.5 x 3.2 cm)
Weight 0.7 lb (0.32 kg)
RoHS Statement Ye s
Warranty 1 year
UNIVERSAL RESISTANCE TRANSDUCER
RES-1E SERIES
DESCRIPTION
The RES-1E Series universal resistance transducer provides
a precision resistance output for DDC control of electric
actuators or other electronic devices that operate from a
variable resistive circuit. Various selectable analog and
pulse-width modulated (PWM) inputs are available, and the
transducer may be powered from 24 VAC or 24 VDC. The
RES-1E is furnished with snap-track for easy mounting.
FEATURES
Ideal for controlling electric actuators
Replaces potentiometer or temperature sensor in
boiler/chiller reset circuits
0-20 mA, 4-20 mA, 0-5V, 1-5V, 0-10V, 2-10V, 0-15V, 3-15
VDC or PWM input signals, DIP switch selectable
AC/DC powered
Replaces motorized slide-wire potentiometer controller
0-135, 0-270, 0-500, and 0-1000 standard outputs,
custom ranges available
Snap-track mounting
Failsafe mode and signal loss feature
LED indication
OPERATION
The RES-1E simulates a three-wire potentiometer output
proportional to an analog or PWM input signal. The resistance
between output terminals B and R increases (W and R
decreases) as the input signal increases. The resistance
between output terminals B and R decreases (W and R
increases) as the input signal decreases. When 24V power
is interrupted at the RES-1E power terminals, the failsafe
mode internally connects the output terminals to the fallback
pot terminals, allowing an alternate back-up controller or
potentiometer to be used for control.