Specifications
NEW!
1417
TRANSDUCERS
TRANSDUCERS
23
WE MAKE IT EASY.
kele.com 888-397-5353 USA
March 2014
Supply Voltage None, loop powered
Input 4-20 mA
Input Impedance 500Ω @ 4-20 mA
Wiring Terminations Screw terminals
Air Capacity 515 scim (135 cm
3
/s) @ 20 psig
(138 kPa) supply
Air Connections 1/4" OD tubing with inline filter
Air Consumption .008 scfm (3.8 cm
3
/s) @ 20 psig
(138 kPa) supply
Maximum Pressure 25 psig (172 kPa)
Linearity 2% of span
Hysteresis 1% of span
Output 3-15 psig (21-103 kPa)
Operating Temperature 32° to 122°F (0° to 50°C)
Operating Humidity 5 to 95% RH (non-condensing)
Weight 0.6 lb (0.27 kg)
Warranty 18 months
CURRENT / PNEUMATIC TRANSDUCER
UCP-242
4-20 mA
Signal
in
(cm)
4.63
(11.75)
3.25
(8.3)
Air Connections
Main (Supply): black
Branch (Output): white or clear
–
+
COM
SIG +
Depth: 2 (5.1)
DESCRIPTION
The UCP-242 Current/Pneumatic Transducer provides
low cost pneumatic control of valves, dampers, or other
pneumatic devices. The UCP-242 comes with snap-track
for easy mounting. Quick-disconnect terminals provide easy
wiring removal for servicing. Barbed fittings for 1/4" plastic
tubing and an in-line filter are provided.
FEATURES
• Inline filter provided
• Snap-track mounting
• 1/4" (0.64 cm) barbed tube connectors
• Quick-disconnect terminals
• Loop-powered control
• Excellent linearity
• Low hysteresis
• No calibration required
SPECIFICATIONS
OPERATION
The UCP-242 accepts a 4-20 mA signal and outputs 3-15
psig. The unit is loop-powered, requiring no power supply
for controlling pneumatic devices. Upon a loss of signal, the
UCP-242 will eventually bleed the pressure in the branch
line. This transducer is well suited for the control of small to
medium volume loads, such as small to medium pneumatic
actuators. Large volume loads, such as large pneumatic
actuators, or long tubing runs may also be controlled but will
exhibit a slower response time.
DIMENSIONS